Plan Review Notes
Plan Review Notes For Permit 21070167
Permit Number 21070167
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-03 17:20:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21070167
 8/3/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET GN100: THE LIST OF CODES USED IN THE DESIGN
 INCLUDE BOTH THE FBC ACCESSIBILITY 7TH EDITION 2020 AND
 THE 2017 ICC/ANSI A117 WHICH ARE TWO SEPARATE CODE
 STANDARDS. PLEASE NOTE THAT SECTION 806.1 FBC EX
 REQUIRES ALTERATIONS TO COMPLY WITH THE PROVISIONS OF
 THE FBC ACC. PLEASE CHOOSE ONE CODE OR THE OTHER AND
 UPDATE ALL CODE REFERENCES SHOWN ON OTHER PLAN SHEETS.
 IF THE INTENTION IS TO MEET FAIR HOUSING DESIGN
 GUIDELINES, PLEASE NOTE THAT THE CURRENT SAFE HARBOR
 FOR COMPLIANCE USED IS THE 2009 ICC/ANSI A117. FOR THE
 PURPOSES OF THIS REVIEW I WILL BE USING THE 2009
 ICC/ANSI A117.
  
 2) GN100: PLEASE PROVIDE A LIST OF DWELLING UNITS, THE
 UNIT FLOOR LEVELS, AND COMMON AREAS THAT WILL BE
 ALTERED AND IMPROVED IN ACCORDANCE WITH THE CHOSEN
 ACCESSIBILITY STANDARD. INDICATE WHICH ADMINISTRATIVE
 AUTHORITY HAS DETERMINED THE TYPE A DESIGN TO BE USED
 AND THE NUMBER OF DWELLING UNITS TO BE REMODELED.
  
 3) GN101: PLEASE IDENTIFY THE DESIGN STANDARD FOR THE
 TYPICAL DETAILS- SECTION 107.2.1 WPB. IF THE TYPICAL
 DETAILS ARE TO BE USED, AND NOT SITE SPECIFIC DETAILS,
 PLEASE REFERENCE THE SHEET AND DETAILS ON ALL
 APPLICABLE PLAN SHEETS.
  
 A) PROVIDE THE STRUCTURAL STRENGTH OF THE GRAB BARS IN
 THE MOUNTING DETAIL - SECTION 609.8 2009 ICC/ANSI A117.
  
 4) GN102 & A805- 2009 ICC/ANSI A117:
  
 A) SHOW THE LOCATION OF THE LAVATORY ON GN 102- SECTION
 1002.11.2.
  
 B) PROVIDE THE TURNING CIRCLE DIAMETER- 1003.3.2.
  
 C) THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET
 IS 60 INCHES MINIMUM IN WIDTH MEASURED PERPENDICULAR
 FROM THE SIDE WALL, AND 56 INCHES MINIMUM IN DEPTH FROM
 THE REAR WALL- 1003.11.2.4.2 & 1003.11.2.4.3. THE CLEAR
 FLOOR SPACE SHALL NOT OVERLAP THE LAVATORY-
 1003.11.2.4.4 UNLESS MEETING THE EXCEPTION. PLEASE
 PROVIDE EVIDENCE OF COMPLIANCE.
  
 D) SHOW THE MAXIMUM DISTANCE FROM THE SHOWER SIDE WALLS
 TO THE GRAB BARS- FIGURE 608.3.2.
  
 E) THE CONTROLS AND HAND SHOWER SHALL BE LOCATED ON THE
 BACK WALL OF THE SHOWER ABOVE THE GRAB BAR, 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND 16 INCHES MINIMUM
 AND 27 INCHES MAXIMUM FROM THE END WALL BEHIND THE SET-
 SECTION AND FIGURE 608.4.2.
  
 F) THE HORIZONTAL GRAB BARS SHALL BE INSTALLED 33
 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISHED
 BATHROOM FLOOR AND SHOWER FLOOR TO THE TOPS OF THE
 GRIPPING SURFACES- 609.4
  
 G) SHOW THE SHOWER SEAT DIMENSIONS AND EDGE CLEARANCE
 DISTANCES IN ACCORDANCE WITH SECTION AND FIGURE
 610.3.1.
  
 H) PROVIDE DETAILS FOR THE KITCHEN SINK REMOVAL CABINET
 INDICATING COMPLIANCE WITH SECTION 1003.12.4.1 ITEMS 1
 & 2 (A, B, & C).
  
 5) GN103 & A806: 2009 ICC/ANSI A117:
  
 A) SHOW THE LOCATION OF THE LAVATORY- SECTION
 1002.11.2.
  
 B) PROVIDE THE TURNING CIRCLE DIAMETER- 1003.3.2. THE
 TURNING CIRCLE IS SHOWN OVERLAPPING THE SHOWER FLOOR.
 PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH SECTION
 303 FOR THE SHOWER THRESHOLD, AND THE REQUIRED KNEE AND
 TOE CLEARANCES AT THE SHOWER SEAT- 304.3 & 306.
  
 C) THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET
 IS 60 INCHES MINIMUM IN WIDTH MEASURED PERPENDICULAR
 FROM THE SIDE WALL, AND 56 INCHES MINIMUM IN DEPTH FROM
 THE REAR WALL- 1003.11.2.4.2 & 1003.11.2.4.3. THE CLEAR
 FLOOR SPACE SHALL NOT OVERLAP THE LAVATORY-
 1003.11.2.4.4 UNLESS MEETING THE EXCEPTION. PLEASE
 PROVIDE EVIDENCE OF COMPLIANCE.
  
 D) SHOW THE MAXIMUM DISTANCE FROM THE SHOWER SIDE WALLS
 TO THE GRAB BARS- FIGURE 608.3.2.
  
 E) THE CONTROLS AND HAND SHOWER SHALL BE LOCATED ON THE
 BACK WALL OF THE SHOWER ABOVE THE GRAB BAR, 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND 16 INCHES MINIMUM
 AND 27 INCHES MAXIMUM FROM THE END WALL BEHIND THE SET-
 SECTION AND FIGURE 608.4.2.
  
 F) THE HORIZONTAL GRAB BARS SHALL BE INSTALLED 33
 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISHED
 BATHROOM FLOOR AND SHOWER FLOOR TO THE TOPS OF THE
 GRIPPING SURFACES- 609.4
  
 G) SHOW THE SHOWER SEAT DIMENSIONS AND EDGE CLEARANCE
 DISTANCES IN ACCORDANCE WITH SECTION AND FIGURE
 610.3.1.
  
 H) PROVIDE DETAILS FOR THE KITCHEN SINK REMOVAL CABINET
 INDICATING COMPLIANCE WITH SECTION 1003.12.4.1 ITEMS 1
 & 2 (A, B, & C).
  
 6) A101.A: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE LOUNGE SINK- SECTION 606.2.
  
 7) A101.B: PROVIDE ENLARGED MEN'S AND WOMEN'S BATHROOM
 DRAWINGS INDICATING PLUMBING FIXTURE INSTALLATION
 COMPLIANCE WITH THE FBC ACCESSIBILITY CODE- 2020. BASED
 ON THE PLANS IT APPEARS THESE BATHROOMS ARE FOR BOTH
 PRIVATE AND PUBLIC USE. PLEASE SEE SECTION 213.3 AND
 PROVIDE DRAWINGS AND DETAILS IN COMPLIANCE WITH THE FBC
 ACC:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 8) P101, P102, P103: PROVIDE SANITARY DRAINAGE AND VENT
 AND WATER SUPPLY RISER DRAWINGS FOR THE NEW PLUMBING
 FIXTURE INSTALLATIONS IN THE NEW LOUNGE AND THE
 REMODELED ACCESSIBLE DWELLING UNITS- SECTION
 107.3.5.1.3 WPB.
  
 9) P101 NEW ENTRY CANOPY ROOF DRAINAGE- SECTION 1101
 FBC P.
  
 A) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF PRIMARY
 AND SECONDARY ROOF DRAINS, THE DRAINAGE FLOW PATTERNS,
 AND SQUARE FOOTAGE AND GPM FLOW CALCULATIONS.
  
 B) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
  
 C) PROVIDE SIZING CALCULATIONS FOR THE PRIMARY VERTICAL
 LEADERS AND HORIZONTAL BRANCHES BASED ON SECTIONS
 1106.1 & 1106.2.
  
 D) PROVIDE SIZING CALCULATIONS FOR THE SECONDARY ROOF
 DRAINS- SECTION 1108.3.
  
 E) PROVIDE PRIMARY AND SECONDARY ROOF DRAIN
 INSTALLATION DETAILS- SECTIONS 1105.1, 1106.5, &
 1108.1.
  
 F) PROVIDE CIVIL PLANS SHOWING POINTS OF CONNECTIONS TO
 EXISTING SANITARY SEWER AND STORM DRAIN MAINS- SECTION
 107.2.1 WPB.
  
 G) PROVIDE A RISER DRAWING- SECTION 107.3.5.1.3 WPB.
  
 10) P201: PROVIDE A PLUMBING FIXTURE SCHEDULE SHOWING
 THE MAKES AND MODELS OF WATER CLOSETS, LAVATORIES,
 SINKS, FAUCETS, SHOWER VALVES, TUB AND SHOWER VALVES,
 ARE MEETING COMPLIANCE WITH THE 2009 ICC/ANSI A117
 STANDARD.
  
 11) P101: WASTE STACK OFFSETS ARE PROHIBITED BETWEEN
 THE LOWEST FIXTURE DRAIN AND HIGHEST FIXTURE DRAIN
 CONNECTIONS- SECTION 913 FBC P.
  
 12) P301: PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAILS FOR PIPE PENETRATIONS ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. THE
 DETAIL PROVIDED DOES NOT MEET COMPLIANCE.
  
 13) P401: PROVIDE CAST IRON PIPE AND FITTING
 SPECIFICATIONS IN COMPLIANCE WITH SECTION 303.5 P.
  
 CAST-IRON SOIL PIPES AND FITTINGS, AND THE COUPLINGS
 USED TO JOIN THESE PRODUCTS TOGETHER, SHALL BE
 THIRD-PARTY LISTED AND LABELED. THIRD-PARTY CERTIFIERS
 OR INSPECTORS SHALL COMPLY WITH THE MINIMUM INSPECTION
 REQUIREMENTS OF ANNEX A OR ANNEX A1 OF THE ASTM AND
 CISPI PRODUCT STANDARDS INDICATED IN THE CODE FOR SUCH
 PRODUCTS.
  
 14) PROVIDE THE INTERIOR WALL SURROUND FINISH DETAILS
 FOR THE WATER CLOSETS IN ACCORDANCE WITH SECTION 310.3
 FBC P SECTION 1210.2.2 FBC B.
  
 15) P106: PROVIDE A NEW ROOF DRAIN INSTALLATION DETAIL-
 SECTION 1105.1 FBC P.
  
 16) P106: PLEASE ADD A NOTE OR REVISE THE NOTES TO
 CLARIFY IF THE WATER HEATERS ARE BEING REPLACED IN THE
 EXACT SAME LOCATIONS OR BEING RELOCATED. PROVIDE A
 PIPING DIAGRAM SHOWING WATER PIPING POINTS OF
 CONNECTIONS TO EXISTING PIPING, AND THE LOCATIONS OF
 THE NEW EXPANSION TANK, RECIRCULATION PUMP, CHECK
 VALVES, DRAIN PANS, PAN DRAIN LINE RUNS AND DISCHARGE
 LOCATIONS- SECTIONS 502, 607.2 & 607.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  