| 2021-07-22 08:44:11 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070167 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE INFORMATION ON ALL OF THE EXISTING | | | MECHANICAL SYSTEMS. ARE THE NEW SYSTEMS A LIKE FOR LIKE | | | CHANGE OUT? FBC 107.2.1 | | | | | | 2) PLEASE SHOW THE EXISTING CONDENSATE DRAIN FOR THE | | | NEW UNITS TO DRAIN TO. FBC M 307 | | | | | | 3) SHEET M304: MD-O66 IS FOR A KITCHEN ROOF EXHAUST FAN | | | DETAIL, PLEASE REFERENCE WHERE THE KITCHEN IS LOCATED | | | FOR THIS PROJECT. FBC 107.2.1 | | | | | | 4) SHEET M101: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS | | | FOR THE NEW GROUND FLOOR LAYOUT. IT SHOULD BE FOR EACH | | | USE OF SPACE ON THE GROUND FLOOR. FBC M 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|