| 2021-08-03 18:08:02 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21070167 |
| | 8/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P201: PLEASE INCLUDE THE WATER HEATER EFFICIENCY |
| | RATINGS IN THE SCHEDULE- TABLE C404.1 FBC EC. |
| | |
| | 2) P201: SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE NEW WATER HEATERS- SECTION |
| | 624.1 FBC FG. |
| | |
| | 3) PD106 & P106: PLEASE ADD A NOTE OR REVISE THE NOTES |
| | TO CLARIFY IF THE WATER HEATERS ARE BEING REPLACED IN |
| | THE EXACT SAME LOCATIONS OR BEING RELOCATED- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) P106: PROVIDE A GAS PIPING PLAN AND RISER DRAWING |
| | SHOWING COMPLIANCE WITH THE FBC FG AND SECTION |
| | 107.3.5.15 WPB. PLEASE SHOW: |
| | |
| | A) THE POINT OF CONNECTION TO THE EXISTING GAS PIPING |
| | SYSTEM. |
| | |
| | B) TYPE OF GAS- NATURAL OR LP AND SYSTEM PRESSURE. |
| | |
| | C) TOTAL BTU LOAD AND WATER HEATER BTU LOADS. |
| | |
| | D) TYPES AND SIZES OF GAS PIPING. |
| | |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | |
| | H) INLET AND OUTLET PRESSURES AT REGULATORS. |
| | |
| | I) PIPE SIZING TABLES FOR ALL NEW PIPING INSTALLATIONS. |
| | |
| | 3) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE |
| | WATER HEATERS AND PROVIDE CALCULATIONS- SECTION 304.1 |
| | FBC FG. |
| | |
| | 4) PROVIDE A VENTING DIAGRAM IN COMPLIANCE WITH SECTION |
| | 624.1 AND 503.3.2 FBC FG. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |