Plan Review Notes
Plan Review Notes For Permit 21070167
Permit Number 21070167
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-27 11:10:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF A FIRE SPRINKLER
 INSTALLATION; HOWEVER, THE FS ARE NOT INDICATED IN
 REQUIRED AREAS.
  
 PER NFPA 1
  
 11.8.3 EXTINGUISHING REQUIREMENTS.
 11.8.3.1* HIGH-RISE BUILDINGS SHALL BE PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH
 SECTION 9.7. A SPRINKLER CONTROL VALVE AND A WATERFLOW
 DEVICE SHALL BE
 PROVIDED FOR EACH FLOOR.
 A.11.8.3.1 WHERE AN OCCUPANCY CHAPTER (CHAPTERS 12
 THROUGH 42) PERMITS
 THE OMISSION OF SPRINKLERS IN SPECIFIC SPACES, SUCH AS
 SMALL BATHROOMS
 AND CLOSETS IN RESIDENTIAL OCCUPANCIES, THE BUILDING IS
 STILL
 CONSIDERED TO BE PROTECTED THROUGHOUT FOR THE PURPOSES
 OF 11.8.3.1.
  
  
 PER NFPA 101 CH 31 EXISTING APARTMENT OCCUPANCIES
  
 31.3.5.2* WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 31.3.5.3 AND 31.3.5.4.
 IN BUILDINGS FOUR OR
 FEWER STORIES IN HEIGHT AND NOT EXCEEDING 60 FT (18.3
 M) IN HEIGHT ABOVE
 GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R SHALL
 BE PERMITTED.
  
 31.3.5.12 HIGH-RISE BUILDING SPRINKLERS.
 31.3.5.12.1 ALL HIGH-RISE BUILDINGS, OTHER THAN THOSE
 MEETING 31.3.5.12.2
 OR 31.3.5.12.3, SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 31.3.5.2.
  
  
 ST. ANDREWS HAS NOT PROVIDED AN ELSS FOR THE
 MODIFICATIONS TO THEIR FS SYSTEM.
 THIS AHJ DOES NOT HAVE RECORD THAT THE RESIDENTS/OWNERS
 HAVE OPTED OUT OF THE FLORIDA RETROFIT
 REQUIRMENTS THRUS A FIRE SPRINKLER SYSTEM SHALL BE
 INSTALLED.
  
 31.3.5.12.3* AN AUTOMATIC SPRINKLER SYSTEM SHALL NOT BE
 REQUIRED IN
 BUILDINGS HAVING AN APPROVED, ENGINEERED LIFE SAFETY
 SYSTEM IN ACCORDANCE
 WITH 31.3.5.12.4.
  
 31.3.5.12.4 WHERE REQUIRED BY 31.3.5.12.3, AN
 ENGINEERED LIFE SAFETY
 SYSTEM SHALL BE DEVELOPED BY A REGISTERED PROFESSIONAL
 ENGINEER EXPERIENCED
 IN FIRE AND LIFE SAFETY SYTEM DESIGN, SHALL BE APPROVED
 BY THE
 AUTHORITY HAVING JURISDICTION, AND SHALL INCLUDE ANY OR
 ALL OF THE
 FOLLOWING:
 (1) PARTIAL AUTOMATIC SPRINKLER PROTECTION
 (2) SMOKE DETECTION SYSTEMS
 (3) SMOKE CONTROL SYSTEMS
 (4) COMPARTMENTATION
 (5) OTHER APPROVED SYSTEMS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) ONLY ONE STAIR HAS AN INDICATION OF A STANDPIPE.
  
 PER NFPA 1
  
 11.8.3.2 HIGH-RISE BUILDINGS SHALL BE PROTECTED
 THROUGHOUT BY A CLASS I
 STANDPIPE SYSTEM IN ACCORDANCE WITH SECTION 9.10.
  
 9.10 STANDPIPE SYSTEMS
 9.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 STANDPIPE AND
 HOSE SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH NFPA
 14.
 9.10.2 WHERE STANDPIPE AND HOSE SYSTEMS ARE INSTALLED
 IN COMBINATION
 WITH AUTOMATIC SPRINKLER SYSTEMS, INSTALLATION SHALL BE
 IN ACCORDANCE
 WITH THE APPROPRIATE PROVISIONS ESTABLISHED BY NFPA 13
 AND NFPA 14.
  
 NFPA 14
  
 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE
 PROVIDED WITH
 21?2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING
 LOCATIONS:
 (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS
 (2) ON EACH SIDE OF THE WALL ADJACENT TO THE EXIT
 OPENINGS OF
 HORIZONTAL EXITS
 (3) IN OTHER THAN COVERED MALL BUILDINGS, IN EACH EXIT
 PASSAGEWAY
 AT THE ENTRANCE FROM THE BUILDING AREAS INTO THE
 PASSAGEWAY
 (4) IN COVERED MALL BUILDINGS, AT THE ENTRANCE TO EACH
 EXIT
 PASSAGEWAY OR EXIT CORRIDOR, AND AT THE INTERIOR SIDE
 OF
 PUBLIC ENTRANCES FROM THE EXTERIOR TO THE MALL
 (5)*AT THE HIGHEST LANDING OF STAIRWAYS WITH STAIRWAY
 ACCESS TO A
 ROOF, OR ON ROOFS WITH A SLOPE OF LESS THAN 4 IN 12
 WHERE
 STAIRWAYS DO NOT ACCESS THE ROOF
 7.3.2.1 HOSE CONNECTIONS SHALL BE PERMITTED TO BE
 LOCATED AT
 THE HIGHEST INTERMEDIATE LANDINGS BETWEEN FLOOR LEVELS
 IN EXIT
 STAIRWAYS WHERE REQUIRED BY THE AHJ.
 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NONSPRINKLERED
 FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M)
 OF TRAVEL
 DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A
 REQUIRED
 EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR
 OR STORY
 IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL
 DISTANCE FROM A
 HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT,
 ADDITIONAL
 HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED
 LOCATIONS,
 WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ.
  
 PLEASE REVIEW AND PROVIDE A STANDPIPE IN EACH STAIRWELL
 OR PROVIDE APPLICABLE DETAILS IN COMPLIANCE WITH CODE.
  
  
  
 3) SHOULD IT BE INTENDED FOR THE BUILDING TO REMIAN
 OCCUPIED, THERE ARE NO LIFE SAFETY PLAN SHEETS
 INDICATING HOW THE EXITS/EXIT ROUTES WILL BE MAINTAINED
 DURING CONSTRUCTION.
  
 ADDITIONALLY, WITH ALL THE EXTERIOR WORK HOW WILL THE
 AREA BE PROTECTED FROM FALLING OR ACCUMULATED
 CONSTRUCTION DEBRIS.
  
 PER NFPA 1
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN
 PLACE AND CONTINUOUSLY MAINTAINED FOR THE PORTION
 OCCUPIED OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION
 ARE IN PLACE.
  
 4.6.10.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43,
 CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241
  
 4.6.10.3* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE
 ESCAPE FACILITIES
 SHALL BE MAINTAINED AT ALL TIMES FOR THE USE OF
 CONSTRUCTION WORKERS.
 ESCAPE FACILITIES SHALL CONSIST OF DOORS, WALKWAYS,
 STAIRS, RAMPS, FIRE
 ESCAPES, LADDERS, OR OTHER APPROVED MEANS OR DEVICES
 ARRANGED IN
 ACCORDANCE WITH THE GENERAL PRINCIPLES OF THE CODE
 INSOFAR AS THEY CAN
 REASONABLY BE APPLIED TO BUILDINGS UNDER CONSTRUCTION.
  
 PLEASE PROVIDE SPECIFIC DETAILS PROVIDING LIFE SAFETY.
  
  
  
 4) THE ELECTRICAL PLAN SHEETS INDICATE FIRE ALARM
 EQUIPMENT.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEGEMENT.
  
  
  
 5) ELECTRICAL SHEETS - THERE ARE NO OF SMOKE ALARMS
 WITHIN THE INDIVIDUAL UNIT.
  
 PER NFPA 101 CH 31
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5, SMOKE
 ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA IN
 ACCORDANCE WITH
 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO
 BE BATTERY POWERED.
  
 9.6.2.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS
 CODE, SINGLESTATION
 AND MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE WITH
 NFPA 72 UNLESS OTHERWISE PROVIDED IN 9.6.2.10.3,
 9.6.2.10.4, 9.6.2.10.6,
 OR 9.6.2.10.7.
 9.6.2.10.2 WHERE AUTOMATIC SMOKE DETECTION IS REQUIRED
 BY CHAPTERS 11
 THROUGH 43, SMOKE ALARMS SHALL NOT BE USED AS A
 SUBSTITUTE.
 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL
 APPLY ONLY TO
 NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.9.
  
 SHOULD IT BE INTENDED TO PROVIDE NEW SMOKE ALARMS IN
 ALL THE UNITS THEN INTERCONNECTION WOULD APPLY.
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL