2021-09-11 14:01:37****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 803.11, PLEASE SHOW THE FIRE CLASSIFICATION
 FOR WALL AND CEILING FINISHES. PLAN SHEET A800.A.
 GENERAL NOTES REFER TO (IBC) CODE SECTIONS. THE
 REQUIRED FIRE CLASSIFICATION NEEDS TO BE ON THE FINISH
 SCHEDULES FOR WALL AND CEILING AREAS.
 2) FBC B 1004.4, PLEASE SHOW, UNDER DESIGN OCCUPANT
 LOAD ON PLAN SHEET GN100, THE OCCUPANT LOAD FOR THE 1ST
 FLOOR COMMUNITY ROOM.
 3) FBC B 107.2.1, PLEASE ADD NOTE, UNDER SCOPE OF WORK
 ON PLAN SHEET GN100, NO FLOORING WILL BE REPLACED AND
 REMOVE THE FLOORING TILE SECTIONS FROM TILE SCHEDULE ON
 SHEET A800.A OR PROVIDE ON PLAN THE UNDERLAYMENT THAT
 WILL BE USED FOR FLOORING REPLACEMENT INCLUDING THE
 TEST REPORTS FOR SOUND AND FLAME SPREAD IN ACCORDANCE
 WITH FBC B 1207.2, 1207.3 & 603.1.
 4) OK, AS DEFERRED SUBMITTAL HAS BEEN INDICATED ON
 PLAN.
 5) FBC B 107.2.1, PLEASE PROVIDE THE, DESIGNER OF
 RECORD REVIEW STAMP APPROVED, PRODUCT APPROVALS FOR THE
 NEW EXTERIOR WINDOWS, DOORS, LOUVERS AND ROOFING
 SYSTEMS & MATERIALS.
 6) NOTE: ALL SHOP DRAWINGS AND PRODUCT APPROVALS MUST
 BE REVIEWED/APPROVED BY DESIGNER OF RECORD
 (ACKNOWLEDGED ON RESPONSE SHEET).
 7) OK, THE CONSTRUCTION TYPE HAS BEEN ADDED TO PLAN
 SHEET GN100.
 8) NOTE: WPB/FBC B 107.3.4.1, DEFERRED SUBMITTAL
 REQUIREMENTS HAVE BEEN ACKNOWLEDGED BY ENGINEER JEREMY
 M. CASE P.E.