| 2021-09-11 14:01:37 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1) FBC B 803.11, PLEASE SHOW THE FIRE CLASSIFICATION |
| | FOR WALL AND CEILING FINISHES. PLAN SHEET A800.A. |
| | GENERAL NOTES REFER TO (IBC) CODE SECTIONS. THE |
| | REQUIRED FIRE CLASSIFICATION NEEDS TO BE ON THE FINISH |
| | SCHEDULES FOR WALL AND CEILING AREAS. |
| | 2) FBC B 1004.4, PLEASE SHOW, UNDER DESIGN OCCUPANT |
| | LOAD ON PLAN SHEET GN100, THE OCCUPANT LOAD FOR THE 1ST |
| | FLOOR COMMUNITY ROOM. |
| | 3) FBC B 107.2.1, PLEASE ADD NOTE, UNDER SCOPE OF WORK |
| | ON PLAN SHEET GN100, NO FLOORING WILL BE REPLACED AND |
| | REMOVE THE FLOORING TILE SECTIONS FROM TILE SCHEDULE ON |
| | SHEET A800.A OR PROVIDE ON PLAN THE UNDERLAYMENT THAT |
| | WILL BE USED FOR FLOORING REPLACEMENT INCLUDING THE |
| | TEST REPORTS FOR SOUND AND FLAME SPREAD IN ACCORDANCE |
| | WITH FBC B 1207.2, 1207.3 & 603.1. |
| | 4) OK, AS DEFERRED SUBMITTAL HAS BEEN INDICATED ON |
| | PLAN. |
| | 5) FBC B 107.2.1, PLEASE PROVIDE THE, DESIGNER OF |
| | RECORD REVIEW STAMP APPROVED, PRODUCT APPROVALS FOR THE |
| | NEW EXTERIOR WINDOWS, DOORS, LOUVERS AND ROOFING |
| | SYSTEMS & MATERIALS. |
| | 6) NOTE: ALL SHOP DRAWINGS AND PRODUCT APPROVALS MUST |
| | BE REVIEWED/APPROVED BY DESIGNER OF RECORD |
| | (ACKNOWLEDGED ON RESPONSE SHEET). |
| | 7) OK, THE CONSTRUCTION TYPE HAS BEEN ADDED TO PLAN |
| | SHEET GN100. |
| | 8) NOTE: WPB/FBC B 107.3.4.1, DEFERRED SUBMITTAL |
| | REQUIREMENTS HAVE BEEN ACKNOWLEDGED BY ENGINEER JEREMY |
| | M. CASE P.E. |