| 2021-08-11 17:03:15 | 08/11/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET GN-100, THE 2017 ICC ANSI A117 ACCESSIBLE |
| | AND USABLE BUILDING AND FACILITIES DOES NOT HAVE THE |
| | YEAR 2009 ON IT HAS 2017, WHICH IS NOT CORRECT. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET GN-102; |
| | |
| | A. UNDER TYPE TOILET AND BATHING FACILITIES # ONE, THE |
| | A17.1 SHOULD BE A117.1, AND THE SECTION SAYS 1003.1, |
| | AND IT SHOULD BE 1003.11. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. NUMBER TWO SAYS 1003.11. AND IT SHOULD BE 1003.11.1. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THERE ARE TWO NUMBER FIVES ON THIS SECTION. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. NUMBER FIVE, THE SECOND ONE, SAY 1004.11.2.4, AND |
| | THERE IS NO SUCH SECTION. IT SHOULD BE 1003.11.2.4. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. THE WATER CLOSET CLEAR FLOOR REQUIREMENTS SHOW 48 |
| | INCHES BY 66 INCHES, AND IT SHOULD BE 60 INCHES BY 66 |
| | INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. THE REINFORCEMENT FOR SEAT REFERS TO 608.2.2.3, AND |
| | IT SHOULD BE 610.4. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | G. PLEASE SHOW THE LOCATION FOR CONTROLS STANDARD |
| | ROLL-IN SHOWER ON THE BACK WALL PER THE ANSI |
| | A117.1-2009 SECTION 608.4.2. |
| | |
| | H. THE NEW FLOOR DRAIN REQUIRES A TRAP PRIMER, SO WOULD |
| | YOU PLEASE ADD THAT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | 3. ON SHEET GN-101; |
| | |
| | |
| | A. DETAIL #20 HAS; |
| | |
| | 1. THE MINIMUM UNDER LAV AT 29 INCHES SHOULD BE 27 |
| | INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE IS NO DETAIL FOR THE CONTROLS PER THE |
| | A117.1-2009 SECTION 608.4.2. WOULD YOU PLEASE ADD THIS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THERE IS NO DETAIL FOR THE DIMENSION OF THE GAB BARS |
| | BACKING MAXIMUM FROM THE SIDEWALL AND THE FLOOR PER THE |
| | A117.1-2009 SECTION 608.3.2 9 (OPTIONAL). WOULD YOU |
| | PLEASE PROVIDE DETAIL FOR THEM PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | D. THERE IS NO DETAIL FOR THE HEIGHT OF THE VERTICAL |
| | GRAB BARS REINFORCEMENT. WOULD YOU PLEASE PROVIDE |
| | DETAIL FOR THEM PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. ON SHEET A101; |
| | |
| | A. WOULD YOU PLEASE LABEL UNIT 3 AS AN FHA ALONG WITH |
| | TYPE A PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. IN UNIT THREE, THE LAV IS NOT SHOWN. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. IN THE COMMUNITY LOUNGE 109, THERE IS A SINK. PLEASE |
| | SHOW THE CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES PER |
| | THE 2020 FBC ACCESSIBILITY CODE 7 EDITION. |
| | |
| | D. WOULD YOU PLEASE PROVIDE A SECTIONAL VIEW FOR THE |
| | LOUNGE, UNISEX BATH, MEN'S AND WOMAN'S RESTROOM. WOULD |
| | YOU PLEASE PROVIDE THE GRAB BARS ELEVATION OF ALL |
| | ACCESSIBILITY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | E. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN |
| | ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP |
| | PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | F. IN THE WOMEN'S AND MEN'S RESTROOMS, THE WOMEN'S |
| | ACCESSIBLE WATER CLOSET REQUIRES A LAV SINCE IT HAS |
| | BEEN MOVED. WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE |
| | SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A |
| | TOILET COMPARTMENT, TOILET COMPARTMENT SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT LEAST |
| | 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, AND |
| | WALL-MOUNTED PER THE 2020 FBC ACC SEC. 604.8.1.6 |
| | LAVATORY. |
| | |
| | G. ACCESSIBLE WATER CLOSET WITHIN THE |
| | WHEELCHAIR-ACCESSIBLE COMPARTMENT SHALL BE LOCATED IN |
| | THE CORNER, DIAGONAL TO THE DOOR PER THE 2020 FBC ACC |
| | SEC. 604.8.1.7 WATER CLOSET. |
| | |
| | 5. IN SHEET A102, WOULD YOU PLEASE LABEL UNIT 3 AS AN |
| | FHA ALONG WITH TYPE A PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | 6. ON SHEET A105; |
| | |
| | A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR |
| | REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES |
| | BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU |
| | PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION, |
| | BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT |
| | HAVE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON |
| | THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN |
| | ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP |
| | PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 7. ON SHEET A805; |
| | |
| | A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR |
| | REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES |
| | BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU |
| | PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION, |
| | BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT |
| | HAVE THE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON |
| | THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 8. ON SHEET A813, WOULD YOU PLEASE THE CLEAR FLOOR |
| | SPACE FOR THE KITCHEN SINK PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 9. ON SHEET A820 ON DETAIL 3 AND 4; |
| | |
| | A. THE MINIMUM UNDER LAV AT 29 INCHES, AND IT SHOULD BE |
| | 27 INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 10. ON SHEET P001, THE REFERENCE STANDARD FOR GAS IS |
| | NOT REQUIRED, BUT THE ACCESSIBILITY IS MISSING. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 11. ON SHEET P101; |
| | |
| | A. THE ARCHITECTURAL DRAWING SHOWS A DIFFERENT LAYOUT |
| | FOR THE MEN'S AND WOMEN'S RESTROOMS. THERE IS A LAYOUT |
| | IN A101 THAT SHOWS THE WOMEN'S TOILETS MOVED. THIS |
| | CONSTITUTES NEW CONSTRUCTION, AND THE ACCESSIBILITY |
| | CODE MUST COMPLY WITH A LAV IN THE TOILET ROOM. WOULD |
| | YOU PLEASE CLARIFY AND CORRECT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. THERE ARE FLOOR DRAINS MOTIONED ON EVERY |
| | ARCHITECTURAL PAGE, BUT NO CONNECTION IS SHOWN ON THIS |
| | PLUMBING PAGE. WOULD YOU PLEASE CLARIFY AND CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. PLEASE LABEL ALL UNITS AND RESTROOMS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. THE FHA UNIT FIVE HAS HAD THE LOCATION OF THE LAV |
| | AND TOILET MOVE ALONG WITH A FLOOR DRAIN ADDED, AND IT |
| | IS NOT SHOWN. WOULD YOU PLEASE ADD AND CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 12. ON SHEET P105, THE RESTROOM FOR WOMEN'S AND MEN'S |
| | SAY INSTALL NEW FIXTURES ON EX ROUGH, BUT ON A101 FOR |
| | WOMEN'S, IT HAS A DIFFERENT LAYOUT, THE SAME AS COMMENT |
| | 11. WOULD YOU PLEASE CORRECT OR CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 13. ON SHEET P201, IT SHOWS A GAS WATER HEATER SCHEDULE |
| | BUT COULD NOT FIND ITS LOCATION. WOULD YOU PLEASE |
| | CLARIFY OR CORRECT IF AN ELECTRIC HEATER IS BEING USED |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. ON SHEET P301, PLEASE PROVIDE LISTED FIRE-STOPPING |
| | DETAILS FOR THE PIPPING THROUGH RATED THE FLOORS. |
| | PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE UL |
| | SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 15. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM |
| | FOR THE CHANGES MADE TO UNIT FIVE TO THE SHIFT OF LAV |
| | AND WATER CLOSET LOCATION PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | IF YOU WOULD LIKE TO CONTACT ME AND DISCUSS |
| | CLARIFICATION ON QUESTION COMMENTS IN THIS REVIEW TO |
| | MOVE IT ALONG, PLEASE FEEL FREE TO SO. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |