Plan Review Notes
Plan Review Notes For Permit 21070162
Permit Number 21070162
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-11 17:03:1508/11/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET GN-100, THE 2017 ICC ANSI A117 ACCESSIBLE
 AND USABLE BUILDING AND FACILITIES DOES NOT HAVE THE
 YEAR 2009 ON IT HAS 2017, WHICH IS NOT CORRECT. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET GN-102;
  
 A. UNDER TYPE TOILET AND BATHING FACILITIES # ONE, THE
 A17.1 SHOULD BE A117.1, AND THE SECTION SAYS 1003.1,
 AND IT SHOULD BE 1003.11. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. NUMBER TWO SAYS 1003.11. AND IT SHOULD BE 1003.11.1.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE ARE TWO NUMBER FIVES ON THIS SECTION. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. NUMBER FIVE, THE SECOND ONE, SAY 1004.11.2.4, AND
 THERE IS NO SUCH SECTION. IT SHOULD BE 1003.11.2.4.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE WATER CLOSET CLEAR FLOOR REQUIREMENTS SHOW 48
 INCHES BY 66 INCHES, AND IT SHOULD BE 60 INCHES BY 66
 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. THE REINFORCEMENT FOR SEAT REFERS TO 608.2.2.3, AND
 IT SHOULD BE 610.4. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. PLEASE SHOW THE LOCATION FOR CONTROLS STANDARD
 ROLL-IN SHOWER ON THE BACK WALL PER THE ANSI
 A117.1-2009 SECTION 608.4.2.
  
 H. THE NEW FLOOR DRAIN REQUIRES A TRAP PRIMER, SO WOULD
 YOU PLEASE ADD THAT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 3. ON SHEET GN-101;
  
  
 A. DETAIL #20 HAS;
  
 1. THE MINIMUM UNDER LAV AT 29 INCHES SHOULD BE 27
 INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THERE IS NO DETAIL FOR THE CONTROLS PER THE
 A117.1-2009 SECTION 608.4.2. WOULD YOU PLEASE ADD THIS
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE IS NO DETAIL FOR THE DIMENSION OF THE GAB BARS
 BACKING MAXIMUM FROM THE SIDEWALL AND THE FLOOR PER THE
 A117.1-2009 SECTION 608.3.2 9 (OPTIONAL). WOULD YOU
 PLEASE PROVIDE DETAIL FOR THEM PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. THERE IS NO DETAIL FOR THE HEIGHT OF THE VERTICAL
 GRAB BARS REINFORCEMENT. WOULD YOU PLEASE PROVIDE
 DETAIL FOR THEM PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET A101;
  
 A. WOULD YOU PLEASE LABEL UNIT 3 AS AN FHA ALONG WITH
 TYPE A PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IN UNIT THREE, THE LAV IS NOT SHOWN. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. IN THE COMMUNITY LOUNGE 109, THERE IS A SINK. PLEASE
 SHOW THE CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES PER
 THE 2020 FBC ACCESSIBILITY CODE 7 EDITION.
  
 D. WOULD YOU PLEASE PROVIDE A SECTIONAL VIEW FOR THE
 LOUNGE, UNISEX BATH, MEN'S AND WOMAN'S RESTROOM. WOULD
 YOU PLEASE PROVIDE THE GRAB BARS ELEVATION OF ALL
 ACCESSIBILITY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN
 ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP
 PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. IN THE WOMEN'S AND MEN'S RESTROOMS, THE WOMEN'S
 ACCESSIBLE WATER CLOSET REQUIRES A LAV SINCE IT HAS
 BEEN MOVED. WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE
 SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT, TOILET COMPARTMENT SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT LEAST
 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, AND
 WALL-MOUNTED PER THE 2020 FBC ACC SEC. 604.8.1.6
 LAVATORY.
  
 G. ACCESSIBLE WATER CLOSET WITHIN THE
 WHEELCHAIR-ACCESSIBLE COMPARTMENT SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR PER THE 2020 FBC ACC
 SEC. 604.8.1.7 WATER CLOSET.
  
 5. IN SHEET A102, WOULD YOU PLEASE LABEL UNIT 3 AS AN
 FHA ALONG WITH TYPE A PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 6. ON SHEET A105;
  
 A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR
 REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES
 BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU
 PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION,
 BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT
 HAVE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON
 THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN
 ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP
 PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 7. ON SHEET A805;
  
 A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR
 REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES
 BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU
 PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION,
 BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT
 HAVE THE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON
 THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET A813, WOULD YOU PLEASE THE CLEAR FLOOR
 SPACE FOR THE KITCHEN SINK PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 9. ON SHEET A820 ON DETAIL 3 AND 4;
  
 A. THE MINIMUM UNDER LAV AT 29 INCHES, AND IT SHOULD BE
 27 INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 10. ON SHEET P001, THE REFERENCE STANDARD FOR GAS IS
 NOT REQUIRED, BUT THE ACCESSIBILITY IS MISSING. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. ON SHEET P101;
  
 A. THE ARCHITECTURAL DRAWING SHOWS A DIFFERENT LAYOUT
 FOR THE MEN'S AND WOMEN'S RESTROOMS. THERE IS A LAYOUT
 IN A101 THAT SHOWS THE WOMEN'S TOILETS MOVED. THIS
 CONSTITUTES NEW CONSTRUCTION, AND THE ACCESSIBILITY
 CODE MUST COMPLY WITH A LAV IN THE TOILET ROOM. WOULD
 YOU PLEASE CLARIFY AND CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THERE ARE FLOOR DRAINS MOTIONED ON EVERY
 ARCHITECTURAL PAGE, BUT NO CONNECTION IS SHOWN ON THIS
 PLUMBING PAGE. WOULD YOU PLEASE CLARIFY AND CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE LABEL ALL UNITS AND RESTROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THE FHA UNIT FIVE HAS HAD THE LOCATION OF THE LAV
 AND TOILET MOVE ALONG WITH A FLOOR DRAIN ADDED, AND IT
 IS NOT SHOWN. WOULD YOU PLEASE ADD AND CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 12. ON SHEET P105, THE RESTROOM FOR WOMEN'S AND MEN'S
 SAY INSTALL NEW FIXTURES ON EX ROUGH, BUT ON A101 FOR
 WOMEN'S, IT HAS A DIFFERENT LAYOUT, THE SAME AS COMMENT
 11. WOULD YOU PLEASE CORRECT OR CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13. ON SHEET P201, IT SHOWS A GAS WATER HEATER SCHEDULE
 BUT COULD NOT FIND ITS LOCATION. WOULD YOU PLEASE
 CLARIFY OR CORRECT IF AN ELECTRIC HEATER IS BEING USED
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET P301, PLEASE PROVIDE LISTED FIRE-STOPPING
 DETAILS FOR THE PIPPING THROUGH RATED THE FLOORS.
 PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE UL
 SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 15. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR THE CHANGES MADE TO UNIT FIVE TO THE SHIFT OF LAV
 AND WATER CLOSET LOCATION PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 IF YOU WOULD LIKE TO CONTACT ME AND DISCUSS
 CLARIFICATION ON QUESTION COMMENTS IN THIS REVIEW TO
 MOVE IT ALONG, PLEASE FEEL FREE TO SO.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  