| 2021-08-03 11:12:08 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070162 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET D101 INDICATES A ROOM WITH OFFICES AT THE |
| | FRONT LEFT CORNER OF THE BUILD. SHEET M101 INDICATES |
| | ONLY AN EXISTING AC UNIT. WHAT IS THE USE OF THIS SPACE |
| | NOW? IS THERE GOING TO BE DUCTWORK RAN FROM THE |
| | EXISTING AC? FBC 107.2.1 |
| | |
| | 2) SHEET M201: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS FOR EACH USE OF SPACE ON THE FIRST-FLOOR |
| | BUSINESS SIDE. THERE ARE AREAS THAT WERE OPEN AND ARE |
| | NOW OFFICES. THERE ARE ALSO AREAS THAT WERE OFFICES |
| | THAT NOW APPEAR TO BE OPEN AREAS. FBC M 403.3.1.1 AND |
| | TABLE 403.3.1.1 |
| | |
| | 3) SHEET M101: NEW WORK MECHANICAL FOOT NOTE 6 HAS BEEN |
| | CUT OFF AND CANT BE READ. PLEASE ADJUST. FBC 107.2.1 |
| | |
| | 4) SHEET MD102 AND M102 ARE BOTH LABELED MECHANICAL |
| | 2ND-8TH FLOOR DEMO PLAN, PLEASE LABEL CORRECTLY. FBC M |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |