Plan Review Notes
Plan Review Notes For Permit 21070162
Permit Number 21070162
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-27 13:09:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHOULD IT BE INTENDED FOR THE BUILDING TO REMIAN
 OCCUPIED, THERE ARE NO LIFE SAFETY PLAN SHEETS
 INDICATING HOW THE EXITS/EXIT ROUTES WILL BE MAINTAINED
 DURING CONSTRUCTION.
  
 ADDITIONALLY, WITH ALL THE EXTERIOR WORK HOW WILL THE
 AREA BE PROTECTED FROM FALLING OR ACCUMULATED
 CONSTRUCTION DEBRIS.
  
 PER NFPA 1
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN
 PLACE AND CONTINUOUSLY MAINTAINED FOR THE PORTION
 OCCUPIED OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION
 ARE IN PLACE.
  
 4.6.10.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43,
 CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241
  
 4.6.10.3* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE
 ESCAPE FACILITIES
 SHALL BE MAINTAINED AT ALL TIMES FOR THE USE OF
 CONSTRUCTION WORKERS.
 ESCAPE FACILITIES SHALL CONSIST OF DOORS, WALKWAYS,
 STAIRS, RAMPS, FIRE
 ESCAPES, LADDERS, OR OTHER APPROVED MEANS OR DEVICES
 ARRANGED IN
 ACCORDANCE WITH THE GENERAL PRINCIPLES OF THE CODE
 INSOFAR AS THEY CAN
 REASONABLY BE APPLIED TO BUILDINGS UNDER CONSTRUCTION.
  
 PLEASE PROVIDE SPECIFIC DETAILS PROVIDING LIFE SAFETY.
  
  
  
 2) THE ELECTRICAL PLAN SHEETS INDICATE FIRE ALARM
 EQUIPMENT.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEGEMENT.
  
  
  
 3) ELECTRICAL SHEETS - THERE ARE NO OF SMOKE ALARMS
 WITHIN THE INDIVIDUAL UNIT.
  
 PER NFPA 101 CH 31
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5, SMOKE
 ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA IN
 ACCORDANCE WITH
 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO
 BE BATTERY POWERED.
  
 9.6.2.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS
 CODE, SINGLESTATION
 AND MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE WITH
 NFPA 72 UNLESS OTHERWISE PROVIDED IN 9.6.2.10.3,
 9.6.2.10.4, 9.6.2.10.6,
 OR 9.6.2.10.7.
 9.6.2.10.2 WHERE AUTOMATIC SMOKE DETECTION IS REQUIRED
 BY CHAPTERS 11
 THROUGH 43, SMOKE ALARMS SHALL NOT BE USED AS A
 SUBSTITUTE.
 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL
 APPLY ONLY TO
 NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.9.
  
 SHOULD IT BE INTENDED TO PROVIDE NEW SMOKE ALARMS IN
 ALL THE UNITS THEN INTERCONNECTION WOULD APPLY.
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL