| 2021-07-08 08:35:05 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL2533-R24 HAS BEEN |
| | REVISED TO FL2533-R25. PLEASE PROVIDE A COMPLETE SET. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| | RULE 61G20-3. |
| | 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL2533 R-24 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| | INCLUDE LIMITATIONS PAGE(S). |
| | 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R24 SELECTED SYSTEM NO. W-64 DO NOT |
| | MEET THE EXPOSURE CATEGORY C; ZONE 2 & 3 MINIMUM DESIGN |
| | PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT |
| | MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND |
| | SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 2 & 3. |
| | SYSTEM MUST ALSO INCLUDE INSULATION IF USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE |
| | CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE C. |
| | |