Plan Review Notes
Plan Review Notes For Permit 21070155
Permit Number 21070155
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-03 14:33:021) SHT. A000 - PLUMBING FIXTURE CALCULATION TABLE -
 INDICATE THE OCCUPANCY THAT YOU ARE USING TO CALCULATE
 THE PLUMBING FIXTURE REQUIREMENTS.FOR CALCULATIONS
 INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS
 FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND THEN
 ROUNDED UP TO THE NEXT WHOLE NUMBER.FBC-PLUMBING SEC.
 403.1.1.
 2) THE PLANS ARE NOT SIGNED AND SEALED AS REQUIRED BY
 FL. ADMIN. CODE RULE 61G1-16.003, 61G1-16.005.
 3) THE APPLICATION STATES THAT THIS IS GOING TO BE A
 CATERING BUSINESS BUT THERE IS NO COOKING EQUIPMENT
 SHOWN ON THE PLANS. CLARIFY.
 4) SHT. A100 - THE PLANS SHOW A PAIR OF STACKED WASHER
 / DRYER UNITS. THE WATER SUPPLY VALVES FOR THESE UNITS
 SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING
 SEC.606.33. THE PLANS SHOW THE VALVES BEHIND THE UNITS
 WHICH MAKE THEM INACESSIBLE.
 5) THE PLANS SHOW ONE DRINKING FOUNTAIN. IF A DRINKING
 FOUNTAIN IS TO BE PROVIDED, A MINIMUM OF TWO DRINKING
 FOUNTAINS ARE REQUIRED PER FBC-PLUMBING SEC.410.3 AND
 FBC-ACCESS. SEC.211.2.
 6) SHT. A104 - SHOW THE REQUIRED DISTANCE UNDER THE
 LAVATORY FROM THE FINISH FLOOR.FBC-ACCESS. SEC.
 306.3.1.
 7) SHT. A1105 - SHOW THE HEIGHT OF THE TOILET SEAT
 COVER DISPENSER AND THE PAPER TOWEL DISPENSER. COMPLY
 WITH FBC-ACCESS. SECS.308 & 309. THE OPERABLE PART OF
 THE DISPENSERS SHALL COMPLY.
 8) SHT. A100 - SHOW THE CLEAR FLOOR SPACE DIMENSIONS ON
 THE PLANS (L X W) FOR THE WATER CLOSETS AND LAVATORIES.
 COMPLY WITH FBC-ACCESS. SECS.604.3 AND 606.2.
 9) SHT. P1.1 & SHT.3.1 - SHOW THE PIPING FOR THE
 DRINKING FOUNTAINS AND BOTH TOILET ROOMS ON THE
 SANITARY AND WATER RISER DIAGRAMS.WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) SHT. P0.1 - DETAIL #2 - THE NOTE AT THE INDIRECT
 WASTE PIPE REFERS TO THE 2017 FBC-PLUMBING. THE CODE IN
 EFFECT IS THE 2020 EDITION. PLEASE REVISE THE NOTE.
 11) INDICATE THE INSULATION THICKNESS ON THE WATER
 PIPING.THE THICKNESS SHALL COMPLY WITH FBC-ENERGY
 SEC.C404.4 & TABLE C403.2.10. THE MINIMUM WALL
 THICKNESS SHALL BE 1-INCH.
 12) THE HOT WATER PIPE SIZING SHALL COMPLY WITH THE
 FBC-ENERGY SECS.C404.5 THROUGH C404.5.2.1 DEPENDING ON
 THE COMPLIANCE METHOD CHOSEN.
 13) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINES PER FBC-PLUMBING SEC.1003.6.
 14) SHT. P1.1 - THE 2 COMPARTMENT SINK IN THE
 DISH/PREPARATION ROOM #109 SHALL DISCHARGE THROUGH A
 GREASE INTERCEPTOR. FBC-PLUMBING SEC.1003.1.
 15) SUBMIT GREASE INTERCEPTOR SIZING CALCULATIONS FOR
 THE 2 AND 3 CCOMPARTMENT SINKS TO ENSURE PROPER SIZING.
 FBC-PLUMBING SEC.1003.2.
 16) SHT. P3.1 - THE WASTE STACKS FOR THE WASHING
 MACHINES SHALL BE A MINIMUM OF 3 INCHES PER
 FBC-PLUMBING SEC.406.2.
 17) IT APPEARS THAT A RECIRCULATION LINE IS REQUIRED ON
 THE WATER PIPING SYSTEM PER FBC-PLUMBING SEC.607.2.
 SHOW THE RECIRCULATION LINE ON THE WATER RISER
 DIAGRAM.COMPLY WITH FBC-ENERGY SEC. C404.6.
 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COOKING EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 19) IF ANY OF THE COOKING EQUIPMEENT IS GAS OPERATED,
 SUBMIT A COMPLEETE GAS PLAN AND GAS RISER FIOR
 REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 20) OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND
 NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY
 INTO THE CIRCULATION PATH. THIS APPLIES TO THE DRINKING
 FOUNTAINS.FBC-ACCESS. SEC. 307.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  