Text |
| 2021-08-03 14:33:02 | 1) SHT. A000 - PLUMBING FIXTURE CALCULATION TABLE - |
| | INDICATE THE OCCUPANCY THAT YOU ARE USING TO CALCULATE |
| | THE PLUMBING FIXTURE REQUIREMENTS.FOR CALCULATIONS |
| | INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS |
| | FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND THEN |
| | ROUNDED UP TO THE NEXT WHOLE NUMBER.FBC-PLUMBING SEC. |
| | 403.1.1. |
| | 2) THE PLANS ARE NOT SIGNED AND SEALED AS REQUIRED BY |
| | FL. ADMIN. CODE RULE 61G1-16.003, 61G1-16.005. |
| | 3) THE APPLICATION STATES THAT THIS IS GOING TO BE A |
| | CATERING BUSINESS BUT THERE IS NO COOKING EQUIPMENT |
| | SHOWN ON THE PLANS. CLARIFY. |
| | 4) SHT. A100 - THE PLANS SHOW A PAIR OF STACKED WASHER |
| | / DRYER UNITS. THE WATER SUPPLY VALVES FOR THESE UNITS |
| | SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING |
| | SEC.606.33. THE PLANS SHOW THE VALVES BEHIND THE UNITS |
| | WHICH MAKE THEM INACESSIBLE. |
| | 5) THE PLANS SHOW ONE DRINKING FOUNTAIN. IF A DRINKING |
| | FOUNTAIN IS TO BE PROVIDED, A MINIMUM OF TWO DRINKING |
| | FOUNTAINS ARE REQUIRED PER FBC-PLUMBING SEC.410.3 AND |
| | FBC-ACCESS. SEC.211.2. |
| | 6) SHT. A104 - SHOW THE REQUIRED DISTANCE UNDER THE |
| | LAVATORY FROM THE FINISH FLOOR.FBC-ACCESS. SEC. |
| | 306.3.1. |
| | 7) SHT. A1105 - SHOW THE HEIGHT OF THE TOILET SEAT |
| | COVER DISPENSER AND THE PAPER TOWEL DISPENSER. COMPLY |
| | WITH FBC-ACCESS. SECS.308 & 309. THE OPERABLE PART OF |
| | THE DISPENSERS SHALL COMPLY. |
| | 8) SHT. A100 - SHOW THE CLEAR FLOOR SPACE DIMENSIONS ON |
| | THE PLANS (L X W) FOR THE WATER CLOSETS AND LAVATORIES. |
| | COMPLY WITH FBC-ACCESS. SECS.604.3 AND 606.2. |
| | 9) SHT. P1.1 & SHT.3.1 - SHOW THE PIPING FOR THE |
| | DRINKING FOUNTAINS AND BOTH TOILET ROOMS ON THE |
| | SANITARY AND WATER RISER DIAGRAMS.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 10) SHT. P0.1 - DETAIL #2 - THE NOTE AT THE INDIRECT |
| | WASTE PIPE REFERS TO THE 2017 FBC-PLUMBING. THE CODE IN |
| | EFFECT IS THE 2020 EDITION. PLEASE REVISE THE NOTE. |
| | 11) INDICATE THE INSULATION THICKNESS ON THE WATER |
| | PIPING.THE THICKNESS SHALL COMPLY WITH FBC-ENERGY |
| | SEC.C404.4 & TABLE C403.2.10. THE MINIMUM WALL |
| | THICKNESS SHALL BE 1-INCH. |
| | 12) THE HOT WATER PIPE SIZING SHALL COMPLY WITH THE |
| | FBC-ENERGY SECS.C404.5 THROUGH C404.5.2.1 DEPENDING ON |
| | THE COMPLIANCE METHOD CHOSEN. |
| | 13) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING |
| | MACHINES PER FBC-PLUMBING SEC.1003.6. |
| | 14) SHT. P1.1 - THE 2 COMPARTMENT SINK IN THE |
| | DISH/PREPARATION ROOM #109 SHALL DISCHARGE THROUGH A |
| | GREASE INTERCEPTOR. FBC-PLUMBING SEC.1003.1. |
| | 15) SUBMIT GREASE INTERCEPTOR SIZING CALCULATIONS FOR |
| | THE 2 AND 3 CCOMPARTMENT SINKS TO ENSURE PROPER SIZING. |
| | FBC-PLUMBING SEC.1003.2. |
| | 16) SHT. P3.1 - THE WASTE STACKS FOR THE WASHING |
| | MACHINES SHALL BE A MINIMUM OF 3 INCHES PER |
| | FBC-PLUMBING SEC.406.2. |
| | 17) IT APPEARS THAT A RECIRCULATION LINE IS REQUIRED ON |
| | THE WATER PIPING SYSTEM PER FBC-PLUMBING SEC.607.2. |
| | SHOW THE RECIRCULATION LINE ON THE WATER RISER |
| | DIAGRAM.COMPLY WITH FBC-ENERGY SEC. C404.6. |
| | 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | COOKING EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 19) IF ANY OF THE COOKING EQUIPMEENT IS GAS OPERATED, |
| | SUBMIT A COMPLEETE GAS PLAN AND GAS RISER FIOR |
| | REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 20) OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND |
| | NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR |
| | GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY |
| | INTO THE CIRCULATION PATH. THIS APPLIES TO THE DRINKING |
| | FOUNTAINS.FBC-ACCESS. SEC. 307.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |