| Plan Review Notes For Permit 21070146 |
| Permit Number |
21070146 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-09-15 12:37:18 | OFFICE ALT. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | LOCATION OF GRAB BAR BACKING SHOULD ALSO BE SHOWN FOR | | | THE SHOWER WALLS - FBC A 608.3 GRAB BARS. | | | GRAB BARS SHALL COMPLY WITH 609 AND SHALL BE PROVIDED | | | IN ACCORDANCE WITH 608.3. WHERE MULTIPLE GRAB BARS ARE | | | USED, REQUIRED HORIZONTAL GRAB BARS SHALL BE INSTALLED | | | AT THE SAME HEIGHT ABOVE THE FINISH FLOOR. | | | EXCEPTIONS: | | | 1.GRAB BARS SHALL NOT BE REQUIRED TO BE INSTALLED IN A | | | SHOWER LOCATED IN A BATHING FACILITY FOR A SINGLE | | | OCCUPANT ACCESSED ONLY THROUGH A PRIVATE OFFICE, AND | | | NOT FOR COMMON USE OR PUBLIC USE PROVIDED THAT | | | REINFORCEMENT HAS BEEN INSTALLED IN WALLS AND LOCATED | | | SO AS TO PERMIT THE INSTALLATION OF GRAB BARS COMPLYING | | | WITH 608.3. |
|