| Plan Review Notes For Permit 21070146 |
| Permit Number |
21070146 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-09 14:36:38 | OFFICE ALT. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING A3.2 SHOWS THE LENGTH OF THE REAR GRAB BAR | | | BACKING INCORRECTLY (NOT LONG ENOUGH) - PLEASE SHOW THE | | | LENGTH OF THE BACKING TO COVER THE GRAB BAR AREA PER | | | FBC 604.5.2 | | | 2) PLEASE PROVIDE A GRAB BAR BACKING DETAIL FBC 609.8 | | | STRUCTURAL STRENGTH. | | | ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS | | | USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS | | | (1112 N) IS APPLIED AT ANY POINT ON THE GRAB BAR, | | | FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE. | | | 3) ROOMS 101, 102, AND 111 - A SWING DOOR IS REQUIRED | | | FOR EGRESS PER FBC 1010.1.2 DOOR SWING. | | | EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED | | | SWINGING TYPE. |
|