| 2022-12-30 09:02:04 | ROOFING REVIEW COMMENTS: |
| | |
| | 1- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ROOFING COVER MATERIAL (NOTE: COORDINATE WITH PLANS. |
| | ELEVATIONS CALL FOR CONCRETE TILE, SECTIONS ON SHEET |
| | A4.0 CALL METAL ROOFING PANELS, WALL SECTIONS CALL FOR |
| | SHINGLES UNDER A ROOF TILE NOTE???. REVISE/CLARIFY ALL |
| | PLANS AS REQUIRED TO MATCH. |
| | B)ROOF UNDERLAYMENT SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | TO AVOID MORE CONFUSION/DEALS PLEASE SUBMIT ALL THE |
| | PRODUCT APPROVALS AS A DEFERRED SUBMITTAL AFTER THE |
| | PERMIT ISSUED AS MENTIONED ON ARCHITECT'S RESPONSE |
| | LETTER. COORDINATE ALL PRODUCT APPROVALS WITH DESIGNER |
| | OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | ARCHITECT'S LETTER STATING THAT HE APPROVES ALL THE |
| | FLORIDA PRODUCT APPROVALS AND NOTICE OF ACCEPTANCE |
| | SUBMITTED IS NOT ACCEPTABLE. THERE IS NO WAY OF KNOWING |
| | WHICH PRODUCT APPROVALS WERE REVIEWED/APPROVED. |
| | WHEN PROVIDING A LETTER FOR PRODUCT APPROVAL REVIEW, |
| | THE ARCHITECT NEEDS TO CLEARLY IDENTIFY EACH SPECIFIC |
| | PRODUCT APPROVAL NUMBER AND MODEL. |
| | A PREFER ALTERNATIVE IS FOR ARCHITECT TO STAMP A REVIEW |
| | STAMP OR TO WRITE ON EACH PRODUCT APPROVAL COVER PAGE |
| | REVIEWED/APPROVED. THIS WAY IT WILL EXPEDITE THE REVIEW |
| | PROCESS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |