Plan Review Notes
Plan Review Notes For Permit 21070135
Permit Number 21070135
Review Stop NFIP
Sequence Number 4
Notes
Date Text
2022-12-29 17:40:00CONSTRUCTION ELEVATION CERTIFICATE REVIEW:
  
 PREVIOUS COMMENT:
 1- REVISE ELEVATION CERTIFICATE SUBMITTED (SEC. 107.2.1
 CITY AMENDMENTS):
 SPECIFY EQUIPMENT PROPOSED ELEVATION.
 PROPOSED ELEVATION IS INCORRECT. PLANS SHOW EQUIPMENT
 IN GARAGE. ALSO, SURVEYOR NEEDS TO DESCRIBE TYPE OF
 EQUIPMENT AND LOCATION AS REQUIRED BY THE ELEVATION
 CERTIFICATE ITEM C2(E).
  
 RESPONSE:
 EQUIPMENT LOCATED IN THE GARAGE IS NOT DESCRIBED. ALSO,
 THERE IS NOT INFORMATION FOR A/C PROPOSED ELEVATION
 (INSIDE AND OUTSIDE UNIT). THIS INFORMATION SHALL BE
 PROVIDED ON THE NOTES SECTION OF SECTION D. SEE FEMA
 ELEVATION CERTIFICATE INSTRUCTIONS AND REVISE AS
 REQUIRED.
  
  
 2- REVISE ITEM A7. BASED ON PLANS SUBMITTED THE
 BUILDING DIAGRAM NUMBER IS 1A NOT 1B. SEE FEMA
 ELEVATION CERTIFICATE INSTRUCTIONS AND REVISE AS
 REQUIRED.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]