| Plan Review Notes For Permit 21070135 |
| Permit Number |
21070135 |
|
| Review Stop |
NFIP |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-12-29 17:40:00 | CONSTRUCTION ELEVATION CERTIFICATE REVIEW: | | | | | | PREVIOUS COMMENT: | | | 1- REVISE ELEVATION CERTIFICATE SUBMITTED (SEC. 107.2.1 | | | CITY AMENDMENTS): | | | SPECIFY EQUIPMENT PROPOSED ELEVATION. | | | PROPOSED ELEVATION IS INCORRECT. PLANS SHOW EQUIPMENT | | | IN GARAGE. ALSO, SURVEYOR NEEDS TO DESCRIBE TYPE OF | | | EQUIPMENT AND LOCATION AS REQUIRED BY THE ELEVATION | | | CERTIFICATE ITEM C2(E). | | | | | | RESPONSE: | | | EQUIPMENT LOCATED IN THE GARAGE IS NOT DESCRIBED. ALSO, | | | THERE IS NOT INFORMATION FOR A/C PROPOSED ELEVATION | | | (INSIDE AND OUTSIDE UNIT). THIS INFORMATION SHALL BE | | | PROVIDED ON THE NOTES SECTION OF SECTION D. SEE FEMA | | | ELEVATION CERTIFICATE INSTRUCTIONS AND REVISE AS | | | REQUIRED. | | | | | | | | | 2- REVISE ITEM A7. BASED ON PLANS SUBMITTED THE | | | BUILDING DIAGRAM NUMBER IS 1A NOT 1B. SEE FEMA | | | ELEVATION CERTIFICATE INSTRUCTIONS AND REVISE AS | | | REQUIRED. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|