2022-07-11 15:27:59NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21070135
  
  
  
 IMPORTANT: REPEAT COMMENT, NOT ADDRESSED:
 PLEASE UPLOAD A SMALLER FILE FOR SHEETS A1.0, A2.0.
 THESE DRAWINGS ARE TOO LARGE AND WE CANNOT PROPERLY
 OPEN AND MARK THEM WHEN PERMIT IS READY FOR ISSUANCE.
 NOTE: THEY HAVE TOO MUCH INFORMATION. BACKGROUND LAYERS
 AND ISOMETRIC DRAWINGS ARE NOT REQUIRED FOR PERMITTING
 PURPOSES. PLEASE DELETE UNNECESSARY INFORMATION. THESE
 APPLIES TO ALL DRAWINGS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD.
  
 PREVIOUS COMMENT:
 A)FLOOR PLAN ON SHEET A2.0 AND FOUNDATION PLAN ON SHEET
 S1 DON'T SPECIFY THE PROPOSED FINISH FLOOR ELEVATION.
 PROVIDE THE REQUIRED INFORMATION. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 PARTIALLY ADDRESSED. SHEET A2.0 SPECIFIES PROPOSED
 FINISHED ELEVATION OF THE MAIN HOUSE BUT IS NOT
 SPECIFYING THE FINISHED FLOOR ELEVATION OF THE GARAGE.
 ALSO, FOUNDATION PLAN ON SHEET S1 DOESN'T SPECIFY THE
 FINISH FLOOR ELEVATION AT THE MAIN HOUSE AND THE
 GARAGE. PROVIDE INFORMATION AS PREVIOUSLY REQUESTED.
  
 PREVIOUS COMMENT:
 B)UNABLE TO OPEN DRAWING A2.0 ON PROJECTDOX. IT LOOKS
 LIKE THE DRAWING IS TOO BIG. REDUCE DRAWING SIZE FOR
 PROPER PLAN REVIEW PROCESSING AND STORAGE. SEC.
 107.2.1.3 CITY AMENDMENTS.
 NOTE: THESE APPLIES TO ALL DRAWINGS. REVISE AS
 REQUIRED.
  
 RESPONSE:
 THESE APPLIES TO ALL DRAWINGS. STILL UNABLE TO OPEN
 DRAWINGS. THEY HAVE TOO MUCH INFORMATION. BACKGROUND
 LAYERS AND ISOMETRIC DRAWINGS ARE NOT REQUIRED FOR
 PERMITTING PURPOSES. PLEASE DELETE UNNECESSARY
 INFORMATION. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PREVIOUS COMMENT:
 C)REVISE ELEVATION CERTIFICATE SUBMITTED (SEC. 107.2.1
 CITY AMENDMENTS):
 (1) OK.
 (2)OK.
 (3)OK.
  
 (4)SPECIFY EQUIPMENT PROPOSED ELEVATION.
 RESPONSE:
 PROPOSED ELEVATION IS INCORRECT. PLANS SHOW EQUIPMENT
 IN GARAGE. ALSO, SURVEYOR NEEDS TO DESCRIBE TYPE OF
 EQUIPMENT AND LOCATION AS REQUIRED BY THE ELEVATION
 CERTIFICATE ITEM C2(E).
  
 NEW COMMENT:
 THERE ARE TWO DIFFERENT DATES WHEN THE SURVEYOR SIGNED
 AND SEALED THE ELEVATION CERTIFICATE. SIGNATURE DATE
 SHOULD BE THE DATE IT WAS SIGNED BY THE SURVEYOR. THESE
 ELEVATION CERTIFICATE WAS REVISED. ONLY THE DATE OF THE
 DIGITAL SIGNATURE SHOULD BE PROVIDED TO AVOID
 CONFLICTS/DELAYS.
  
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE.
 A)OK.
 B)OK.
 C)OK.
  
 D)RETAINING WALL AND PROPOSED FENCES REQUIRED SEPARATE
 PERMITS. SEC. 105.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- OK.
 4- OK.
 5- OK.
 6- OK.
  
 ORIGINAL COMMENT:
 7- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY DONE. REVISED DRAWING E1 DOESN'T SHOW A
 CARBON MONOXIDE ALARM WITHIN 10 FEET OF THE MASTER
 BEDROOM.
  
 8- OK.
 9- OK.
  
 10- STRUCTURAL PLANS:
 A)OK
  
 ORIGINAL COMMENT:
 B)STRUCTURAL PLANS TO SPECIFY ROOF TRUSSES DEAD AND
 LIVE LOADS. CLEARLY SPECIFY TOP AND BOTTOM LOADS.
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CLEARLY SPECIFY TOP
 CHORD LIVE AND DEAD LOADS AND BOTTOM CHORD LIVE AND
 DEAD LOADS. NOTE: SEE FOOTNOTES "B" AND "G" OF TABLE
 R301.5 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 C)STRUCTURAL PLANS SHOW A VENTED ATTIC. COORDINATE WITH
 REVISED ARCHITECTURAL PLANS. IT IS NOT CLEAR IF ATTIC
 IS DESIGNED AS VENTED OR UNVENTED. SEE COMMENT BELOW.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 ARCHITECT NEEDS TO SPECIFY LOCATION OF THE VENTS
 SPECIFIED ON TYPICAL WALL SECTION 1/A5.0. SHOW VENT
 LOCATIONS ON THE ROOF PLAN.
  
 11-SHEET A5.0:
 ORIGINAL COMMENT:
 A)IT IS NOT CLEAR IF BUILDING IS DESIGNED WITH A VENTED
 OR UNVENTED ATTIC. TYPICAL WALL SECTION SHOWS AN
 UNVENTED ATTIC, WHILE THE SECTION AT BOND BEAM DETAIL
 ABOVE THE WALL SECTION SHOWS A VENTED ATTIC.
 REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: IF VENTED, THEN SPECIFY VENT SIZE AND SPACING.
 IF UNVENTED, THEN PROVIDE ICC EVALUATION REPORT FOR THE
 FOAM R-30 INSULATION SPECIFIED BY THE ARCHITECT TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 ARCHITECT NEEDS TO SPECIFY LOCATION OF THE VENTS
 SPECIFIED ON TYPICAL WALL SECTION 1/A5.0. SHOW VENT
 LOCATIONS ON THE ROOF PLAN.
  
  
 ORIGINAL COMMENT:
 B)EXTERIOR DOOR BUCK DETAIL SPECIFIES 1X4 OR 2X4 P.T.
 BUCK. THIS SIZE OF BUCK DOESN'T PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED. BY SEC. R609.7.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 REVISED DETAIL DOESN'T SHOW FULL SUPPORT OF THE DOOR
 FRAME. SIZE OF STRUCTURAL BUCK IS NOT SPECIFIED. THERE
 ARE ONLY SPECIFICATIONS FOR THE BLOCKING PIECE. ALSO,
 COORDINATE WITH DOOR PRODUCT APPROVAL FOR TYPE OF DOOR
 FRAME TO AVOID CONFLICTS/DELAYS.
  
 12- OK.
 13- OK.
  
 ORIGINAL COMMENT:
 14- REVISE THE CODE REFERENCE PROVISION SPECIFIED ON
 SHEET A0.0. THIS SINGLE FAMILY RESIDENCE IS R3 NOT R2.
 SEC. 310.5 FBC-BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 15- ENERGY CALCULATIONS:
 PREVIOUS COMMENT:
 RESPONSE:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (THIS JURISDICTION IS 604700). SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C)OK.
 D)OK.
 E) OK.
  
 ORIGINAL COMMENT:
 F)REVISE THE BUILDING ORIENTATION SPECIFIED FOR WALLS,
 DOORS AND WINDOWS. THE ENTRY DOOR FOR THIS HOUSE IS
 FACING SOUTH NOT NORTH. SEE NORTH ARROW ON PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 G) REVISE DOOR INFORMATION ON PAGE 3 OF 4. IT LOOKS
 LIKE THE GARAGE OVERHEAD DOOR 11'X8' WAS INCLUDED. ONLY
 THE DOORS SEPARATING A/C AREAS FROM NON A/C AREAS ARE
 TO BE CONSIDERED. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 16- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
 B)ROOF UNDERLAYMENT SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS AS SPECIFIED BY THE ARCHITECT OF
 RECORD.
 NOTE: PRODUCT APPROVAL SUBMITTED IS FOR HORIZONTAL
 SLIDING WINDOWS NOT FOR SINGLE HUNG WINDOWS.
  
 ORIGINAL COMMENT:
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 18- OK.
  
 19- INFORMATIONAL:
 SIDEWALK NOTES ON SHEET A1.0 NEED TO BE COORDINATED
 WITH THE ENGINEERING DEPARTMENT. SIDEWALK IS NOT
 INCLUDED IN THIS PERMIT. SEPARATE PERMIT IS REQUIRED.
 COORDINATE NOTES WITH THE ENGINEERING DEPARTMENT.
 SEC. 105.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,