| Plan Review Notes For Permit 21070135 |
| Permit Number |
21070135 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-30 06:33:43 | 1) SHT. A2.0 - FLOOR PLAN NOTE #2 REFERS TO A WHOLE | | | HOUSE TANKLESS WATER HEATER BUT THE FLOOR PLAN AND | | | WATER RISER SHOWS A TANK TYPE WATER HEATER. CLARIFY. | | | 2) SHT. A5.0 - DETAIL #1 REFERS TO RAINWATER | | | CALCULATIONS ON THE ROOF PLAN. THERE ARE NO RAINWATER | | | CALCULATIONS ON THE ROOF PLAN. CLARIFY. | | | 3) RAINWATER SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM | | | THE STRUCTURE SIDEWALL. FBC-RES. SEC. 318.5. | | | 4) SHT. P-1 AND P-2 DO NOT BEAR THE DIGITAL SIGNATURE | | | AND SEAL OF THE DESIGN PROFESSIONAL PER FL. ADMIN. CODE | | | RULE 61G15-23.004, 61G15-23.005. | | | 5) SHT. IR-1 - THE IRRIGATION HEADS SHALL BE LOCATED A | | | MINIMUM OF ONE FOOT FROM THE STRUCTURE SIDEWALL PER | | | FBC-RES.SEC. 318.5. | | | 6) THE RELIEF VALVE DISCHARGE FOR THE WATER HEATER | | | SHALL COMPLY WITH FBC-RES. SEC. P2804.6.1 AND BE | | | LOCATED IN THE SAMEE ROOM AS THE WATER HEATER. | | | 7) AN AIR ARRETOR IS REQUIRED FOR THE DISHWASHER PER | | | FBC-RES. SEC.P2903.5. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|