| Plan Review Notes For Permit 21070133 |
| Permit Number |
21070133 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-26 10:18:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ONE SHEET A1.1 THE WIND DESIGN SPECIFIES ASCE7-10. | | | THE 2020 FBC REFERENCES ASCE7-16. PLEASE REVISE THE | | | PLANS TO REFERENCE THE CURRENT ASCE7 STANDARD. FBC | | | CHAPTER 35 | | | | | | 2) SHOW THAT THE OPENINGS IN THE BALCONY RAILING | | | (GUARDS) AND STAIRWAY RAILING (GUARDS) SHOWN ON SHEET | | | A1.4 WILL COMPLY WITH THE OPENING LIMITATIONS OF | | | FBC-R312.1.3. | | | | | | 3) ON SHEET A1.4 THE ATTACHMENTS FOR THE DECORATIVE | | | SHUTTERS, STAIR/BALCONY RAILINGS PRIVACY SCREEN AND | | | PERGOLA ARE SPECIFIED AS PER MANUFACTURES REQUIREMENTS. | | | THE DESIGNER OF RECORD IS REQUIRED TO SPECIFY THAT | | | THESE CONNECTIONS ARE ABLE TO MEET THE WINDLOADS AND | | | ALL OF THE OTHER LOADS REQUIRED BY THE BUILDING CODE. | | | THE DESIGNER OF RECORD WILL BE REQUIRED TO REVIEW THE | | | ATTACHMENTS SPECIFIED BY THE DELEGATE ENGINEER ON THE | | | SHOP DRAWINGS AND VERIFY IN WRITING THAT THEY WILL | | | COMPLY WITH THE DESIGN LOADS. FBC AMEND. 107.3.4 | | | | | | 4) SEPARATE PERMITS ARE REQUIRED FOR FENCES/FENCE | | | REPAIR. FBC AMEND. 105 |
|