| 2021-08-17 12:58:27 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/RPX306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: ARCHITECTURAL AND STRUCTURAL PLANS SHALL BE |
| | SUBMITTED SEPERATELY. |
| | USE PROPER NAMING CONVENTION FOR FILES. |
| | |
| | 1. PROVIDE A SOILS REPORT. LOT IS LOCATED IN AN AREA OF |
| | QUESTIONABLE SOILS. |
| | 1803.2 INVESTIGATIONS REQUIRED. |
| | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN |
| | ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5. |
| | |
| | 2. IT APPEARS THE STRUCTURE IS LOCATED IN A SPECIAL |
| | FLOOD HAZARD AREA (SFHA), FLOOD ZONE AE WITH A BASE |
| | FLOOD ELEVATION OF 12.2FEET. |
| | PROVIDE A CURRENT BOUNDRY LINE SURVEY SHOWING THE |
| | LOCATION OF THE STRUCTURE AND THE SFHA. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3. ON PLAN PAGE S2, CEILING INSULATION IS SHOWN AS R-30 |
| | BATT. ON PLAN PAGE A5.0, CEILING INSULATION IS SHOWN AS |
| | SPRAY FOAM. PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. ROOF COVERING: PAGE A5.0 SHOWS ASPHALT SHINGLES, |
| | PAGE A3.0 SHOWS CONCRETE TILES. PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5. PROVIDE A SITE DRAINAGE PLAN. |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| | FBC R401.3 DRAINAGE. |
| | |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. |
| | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES WITHIN THE FIRST 10 FEET. |
| | |
| | NOTICE: ROOFING BY SEPERATE PERMIT. PROVISO ON PLAN |
| | PAGE S1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |