| Plan Review Notes For Permit 21070101 |
| Permit Number |
21070101 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-12-02 15:53:57 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW APPROVED WITH PROVISOS: | | | | | | 1.) PROVIDE ENGINEER'S LETTER STATING THAT THIS | | | BUILDING IS OF A CONSTRUCTION TYPE VB. | | | 2.) AT TIME OF INSPECTOR, PROVIDE TO FIELD INSPECTOR | | | THE TRUSS ENGINEERING PACKAGE (REVIEW STAMP APPROVED) | | | BY DESIGNER OF RECORD. | | | 3.) WINDLOADS/WIND DESIGN INFORMATION NEEDS TO BE | | | CHANGED FROM ASCE 7-10 TO ASCE 7-16. | | | 4.) PROVIDE AN ATTIC ACCESS OPENING FROM CEILING. THIS | | | IS TO BE INSPECTED AT TIME OF FIELD INSPECTION. | | | | | | |
|