| Plan Review Notes For Permit 21070078 |
| Permit Number |
21070078 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-08-24 10:18:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PROPOSED TRAILER LOCATION APPEARS TO BE TOO | | | CLOSE TO THE PROPOSED BUILDING PER THE NFPA 241 | | | REQUIREMENT. | | | | | | THE FOUNDATION PLAN INDICATES A LENGTH OF 44', PER THE | | | NFPA 241 TABLE, THE TRAILER IS REQUIRED TO BE SEPARATED | | | FROM THE PROPSED BUILDING AT LEAST 40'. SHOULD FIRE | | | SPRINKLERS BE INSTALLED , A 75% REDUCTION IN THAT WIDTH | | | CAN BE APPLIED. | | | | | | PLEASE REVIEW AND CORRECT. (FYI - ABC DRY CHEMICAL | | | SPRINKLERS CAN BE ACCEPTED IN LIEU OF WATER FIRE | | | SPRINKLERS IF INSTALLED ACCORDING TO MANUFACTURERS | | | SPECIFICATIONS.) | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|