Plan Review Notes
Plan Review Notes For Permit 21070078
Permit Number 21070078
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-08-24 10:18:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED TRAILER LOCATION APPEARS TO BE TOO
 CLOSE TO THE PROPOSED BUILDING PER THE NFPA 241
 REQUIREMENT.
  
 THE FOUNDATION PLAN INDICATES A LENGTH OF 44', PER THE
 NFPA 241 TABLE, THE TRAILER IS REQUIRED TO BE SEPARATED
 FROM THE PROPSED BUILDING AT LEAST 40'. SHOULD FIRE
 SPRINKLERS BE INSTALLED , A 75% REDUCTION IN THAT WIDTH
 CAN BE APPLIED.
  
 PLEASE REVIEW AND CORRECT. (FYI - ABC DRY CHEMICAL
 SPRINKLERS CAN BE ACCEPTED IN LIEU OF WATER FIRE
 SPRINKLERS IF INSTALLED ACCORDING TO MANUFACTURERS
 SPECIFICATIONS.)
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  