2021-09-22 08:46:081ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070024
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 CHANGE OF USE OF THE GARAGE TO A LIVING SPACE. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7.1
  
 3) PLEASE PROVIDE A MECHANICAL DRAWING FOR THE
 MECHANICAL SYSTEM INSTALLATION INCLUDING THE CONDENSING
 UNIT TIE DOWN. FBC 107.2.1
  
 4) PLEASE PROVIDE DETAILS OF THE COOKING EQUIPMENT
 BEING INSTALLED UNDER THE HOOD. FBC 107.2.1
  
 M1302.1 LISTED AND LABELED. APPLIANCES REGULATED BY
 THIS CODE SHALL BE LISTED AND LABELED FOR THE
 APPLICATION IN WHICH THEY ARE INSTALLED AND USED,
 UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH SECTION
 R104.11.
  
 5) THIS IS A RESIDENTIAL BUILDING, PLEASE PROVIDE
 DETAILS FOR THE TYPE 1 HOOD AND SHOW IT CAN BE
 INSTALLED IN A RESIDENTIAL OCCUPANCY. IF THIS CAN BE
 SHOWN PLEASE SHOW DETAILS OF THE HOOD BEING MOUNTED
 WITH THE CLEARANCES TO COMBUSTIBLES. ALONG WITH THE
 GREASE DUCT. FBC 107.2.1
  
 6) A MECHANICAL PERMIT WILL BE REQUIRED FOR THE
 MECHANICAL SYSTEM FOR THIS BUILDING.
  
 7) A SEPARATE MECHANICAL PERMIT WILL BE REQUIRED FOR
 THE HOOD SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  