| Plan Review Notes For Permit 21061843 |
| Permit Number |
21061843 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-07 06:41:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER DIAGRAM SHOW 2/0 CONDUCTORS FOR A 200A | | | SERVICE. 310.15(B)(16) | | | | | | 2) EXAM AND TREATMENT ROOMS TO BE WIRED PER | | | 517.13(A)(B) | | | | | | 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL | | | EQUIPMENT IN PATIENT CARE SPACES. WIRING IN PATIENT | | | CARE SPACES SHALL COMPLY WITH 517.13(A) AND (B). | | | | | | 3) WAITING AREA TO HAVE TAMPER RESISTANT OUTLETS 406.12 | | | | | | 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND | | | 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE | | | RECEPTACLES IN THE AREAS SPECIFIED IN 406.12(1) THROUGH | | | (7) SHALL BE LISTED TAMPERRESISTANT RECEPTACLES | | | (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE | | | LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND | | | OUTPATIENT FACILITIES |
|