2021-07-07 06:41:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM SHOW 2/0 CONDUCTORS FOR A 200A
 SERVICE. 310.15(B)(16)
  
 2) EXAM AND TREATMENT ROOMS TO BE WIRED PER
 517.13(A)(B)
  
 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL
 EQUIPMENT IN PATIENT CARE SPACES. WIRING IN PATIENT
 CARE SPACES SHALL COMPLY WITH 517.13(A) AND (B).
  
 3) WAITING AREA TO HAVE TAMPER RESISTANT OUTLETS 406.12
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS SPECIFIED IN 406.12(1) THROUGH
 (7) SHALL BE LISTED TAMPERRESISTANT RECEPTACLES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND
 OUTPATIENT FACILITIES