2021-07-21 11:05:22STORE REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE SALES COUNTER HEIGHT TO COMPLY WITH
 FBC (A) 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED.
 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS FOR THE WALL
 AND CEILING FINISHES FIRE CLASSIFICATION PER FBC 803.11
 INTERIOR FINISH REQUIREMENTS BASED ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.11 FOR THE GROUP AND LOCATION DESIGNATED.