Plan Review Notes
Plan Review Notes For Permit 21061748
Permit Number 21061748
Review Stop M
Sequence Number 1
Notes
Date Text
2021-07-02 16:49:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061748
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CODE COMPLIANT DRAWINGS FOR THIS
 BUILDING SHOWING THE SPACES BEING CONDITIONED. FBC
 107.2.1
  
 2) AS THE SPACE BEING CONDITIONED IS A WAREHOUSE PLEASE
 PROVIDE THE ENERGY CALCULATIONS. FBC EC C402
  
 3) PLEASE SHOW THE ROOF ACCESS TO THE NEW RTU?S. FBC M
 306.5
  
 4) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH
 USE OF SPACE BASED ON THE FBC M 403.3.1.1 AND TABLE
 403.3.1.1
  
 5) PLEASE SHOW THE CONDENSATION PIPING AND THE
 TERMINATION LOCATION. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved