| Plan Review Notes For Permit 21061748 |
| Permit Number |
21061748 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-22 15:52:15 | NEW AC EQUIPMENT ON ROOF TOP | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE | | | STRUCTURAL ROOF FRAMING COMPONENTS ARE ADEQUATE FOR THE | | | ADDITIONAL LOADS PER FBC EXISTING BUILDING 707.2 | | | ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF | | | EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR | | | REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD | | | LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING | | | OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
|