| 2021-08-16 18:13:21 | 08/16/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET G-103; |
| | A. UNDER THE PLUMBING SYSTEM, PLEASE PROVIDE THE |
| | OCCUPANCY LOAD AND REQUIRED NUMBER OF FIXTURES FOR THE |
| | STRUCTURE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. IF A MOP SINK IS REQUIRES THE SURROUNDING THE WALL |
| | SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 2. PLEASE NOTE THAT THE CITY OF WEST PALM BEACH |
| | REQUIRES A SEPARATE PERMIT FOR A GREASE INTERCEPTOR |
| | ALONG WITH AN ENGINEERING REVIEW. UNDER GREASE |
| | INTERCEPTOR, IT SAYS NOT NEEDED, BUT ON CIVIL AND |
| | ARCHITUAL, IT SHOWS TWO INTERCEPTORS. YOU MAY SUBMIT |
| | THE CALCULATION AT THIS TIME OR HAVE THE VERBIAGE OF |
| | HOW IT WILL BE DONE. WOULD YOU PLEASE CLARIFY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON SHEET G-104; |
| | |
| | A. ON THE LABORATORY AND MIRRORS. WOULD YOU PLEASE SHOW |
| | THE REFLECTIVE PART OF THE MIRROR TO BE THE OF 40 |
| | INCHES TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. |
| | 603.3. |
| | |
| | B. WOULD YOU PLEASE SHOW THE BOTTOM ON THE LAV AT A |
| | MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE 2017 FBC |
| | SEC. 306.3. |
| | |
| | 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE ON THE WATER CLOSET PER THE 2017 FBC |
| | ACC SEC. 609.4. |
| | |
| | 5. ON SHEET A-400; |
| | |
| | A. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE |
| | CLEARANCES FOR LAV, WATER CLOSET PER FLORIDA BUILDING |
| | CODE AND FLORIDA ACCESSIBILITY CODE. |
| | |
| | B. WOULD YOU PLEASE SHOW THE 30 INCHES BY 48 INCHES |
| | INSIDE THE RUNNING RADIUS PER THE 2017 FBC ACC SEC. 305 |
| | CLEAR FLOOR OR GROUND SPACE. |
| | |
| | C. WOULD YOU PLEASE PROVIDE A NOTE FOR DETAIL OF THE |
| | ACCESSIBLE ELEVATIONS DIMENSION ON G-104 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. ON SHEET P-107; |
| | |
| | A. THIS MAY CHANGE DUE TO SIZING CALCULATION IN FUTURE |
| | SPACES. A. A SEPARATE PERMIT APPLICATION AND REVIEW ARE |
| | REQUIRED FROM ENGINEERING FOR THE GREASE INTERCEPTOR. |
| | AT THAT TIME, PLEASE PROVIDE GREASE INTERCEPTOR |
| | SPECIFICATIONS. |
| | |
| | B. TWO SAMPLING PORTS CANNOT BE SHARED PER THE CITY OF |
| | WEST PALM BEACH PUBLIC WORKS DEPARTMENT. |
| | |
| | C. ON THE ISOMETRIC, IT SHOWS A WATER CLOSET ON A TRUNK |
| | LINE WITHOUT BEING VENTED, AND THE END OF THE TRUCK |
| | LINE HAS A FUTURE LABELED. THE WATER CLOSET NEEDS TO BE |
| | VENTED FROM THE LAVS PER THE 2017 FBC SEC. 901.2. |
| | |
| | D. ON THE TWO WATER CLOSETS ON THE SECOND FLOOR, ONE |
| | NEEDS TO HAVE A VENT PER THE 2017 FC 901.2.1 VENTING |
| | REQUIRED. |
| | |
| | 7. WOULD YOU PLEASE PROVIDE LISTED FIRE-STOPPING |
| | DETAILS FOR THE PIPPING THROUGH RATED WALLS AND THE |
| | FLOORS? WOULD YOU PLEASE SUBMIT THE COMPLETE ASSEMBLY |
| | DETAILS FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC |
| | SEC. 107.2.1? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |