| 2021-08-12 16:27:35 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21061741 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS IS A CHANGE OF USE FROM F-2 TO MERCANTILE. | | | PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS | | | PROJECT. FBC EC C402.1 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS PROJECT. FBC EC C403.2.1 | | | | | | 3) SHEET M-001: THERE ARE 7 OUTDOOR UNITS BUT ONLY 5 | | | INDOOR UNITS LISTED. WHY ARE AHU-JS-05 AND AHU-JS-06 | | | MISSING FROM THE SHEET? | | | | | | 4) PLEASE SHOW THE CONDENSATION PIPING FOR THE AHU?S | | | AND THE RTU-21. PLEASE SHOW THE TERMINATION LOCATION | | | FOR EACH. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|