2021-08-12 16:27:352ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21061741
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS A CHANGE OF USE FROM F-2 TO MERCANTILE.
 PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT. FBC EC C402.1
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS PROJECT. FBC EC C403.2.1
  
 3) SHEET M-001: THERE ARE 7 OUTDOOR UNITS BUT ONLY 5
 INDOOR UNITS LISTED. WHY ARE AHU-JS-05 AND AHU-JS-06
 MISSING FROM THE SHEET?
  
 4) PLEASE SHOW THE CONDENSATION PIPING FOR THE AHU?S
 AND THE RTU-21. PLEASE SHOW THE TERMINATION LOCATION
 FOR EACH. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  