| 2021-08-17 16:09:08 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1) PROVIDE NOTES THAT INDICATE, DETAILS FOR THE |
| | PEDESTRIAN BRIDGE CAN BE FOUND ON THE PEDESTRIAN BRIDGE |
| | PERMIT # 21070960. |
| | IS THERE AN APPROVED PLAN/SUBMITTAL, FOR THE BRIDGE, BY |
| | A STATE OR FEDERAL AGENCY RELATED TO THE TRAIN SYSTEM? |
| | |
| | 2) THE CORRIDOR ON THE LIFE SAFETY SHEET (B101) DOES |
| | NOT HAVE INDICATIONS OF WIDTHS/LENGTHS. THE CORRIDOR IS |
| | MISSING IDENTIFICATION ON THE PLAN SHEETS AS AN EXIT |
| | PASSAGEWAY. THIS WILL BE REQUIRED IF IT IS AN EXIT |
| | PASSAGEWAY, PENDING CLASSIFICATION OF SPACES AND |
| | REVISION OF THIS SHEET. |
| | |
| | 3) THE LIFE SAFETY SHEET (B101) NEEDS TO BE REVISED. |
| | THE INFORMATION APPEARS TO HAVE CHANGED FROM MERCANTILE |
| | & WAREHOUSES TO RESTAURANTS AND OR ASSEMBLY. IN ORDER |
| | TO MOVE FORWARD, THIS NEEDS TO BE CLARIFIED AS TO WHAT |
| | IS THE INTENDED USE OF EACH SPACE. |
| | |
| | 4) PROVIDE ALL SHOP DRAWINGS/PRODUCT APPROVALS |
| | INCLUDING: |
| | THE STEEL FRAMING AT THE PRESS ROOM, THE ROOFING |
| | SYSTEM, WINDOWS/DOORS, STOREFRONTS, ... |
| | |
| | 5) A SUB-PERMIT IS REQUIRED FOR ROOFING. |
| | |
| | 6) SEPARATE PERMITS ARE REQUIRED FOR: PARKING/STRIPING |
| | AT PARKING LOT, EXTERIOR SIGNAGE, EXTERIOR CANOPIES, |
| | DUMPSTER ENCLOSURES & GENERATOR. |
| | |
| | 7) A DETAIL FOR THE REINFORCEMENT OF THE LOADING DOCK |
| | AREA ABOVE THE INTERCEPTORS IS REQUIRED AS THIS APPEARS |
| | TO BE AN AREA FOR VEHICLE TRAFFIC. |
| | |
| | 8) A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS |
| | TIME AS MORE INFORMATION IS REQUIRED. |
| | |