Plan Review Notes
Plan Review Notes For Permit 21061733
Permit Number 21061733
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-21 11:54:5707/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1. THE 2015
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. SUBMIT THE POOL PUMP CURVE. IDENTIFY ON THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, THE PUMP, FILTER AND CHLORINATOR PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE
 WILL BE REQUIRED AT THE WATER METER BY A LICENSED
 CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE
 CROSS CONNECTION CONTROL MANUAL PAGE. THE STRUCTURES
 ARE MULTI-FAMILY DWELLINGS, AND WATER USERS WILL BE
 REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT
 THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER. THE HOME OWNER IS RESPONSIBLE
 FOR THIS, SO PLEASE GET IN TOUCH WITH THEM AT
 561-822-2240.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved