| 2021-09-08 17:59:59 | 09/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A1.2, IT IS A 40-GALLON ELECTRIC HEATER, |
| | BUT IT SHOWS A GAS HEATER ON THE HOUSE PLANS. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. |
| | |
| | 3. CONDENSATE NEEDS TO BE 1' AWAY FROM THE STRUCTURE |
| | PER THE 2020 FBC SEC. R318.5. |
| | |
| | 4. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR |
| | SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R |
| | 2903.9.3 FIXTURE VALVES AND ACCESS. |
| | |
| | 5. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER |
| | DIAGRAM FOR SANITARY AND WATER PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING? |
| | |
| | 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |