Plan Review Notes
Plan Review Notes For Permit 21061686
Permit Number 21061686
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-08 17:59:5909/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.2, IT IS A 40-GALLON ELECTRIC HEATER,
 BUT IT SHOWS A GAS HEATER ON THE HOUSE PLANS. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 3. CONDENSATE NEEDS TO BE 1' AWAY FROM THE STRUCTURE
 PER THE 2020 FBC SEC. R318.5.
  
 4. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS.
  
 5. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR SANITARY AND WATER PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING?
  
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  