2021-09-07 06:49:28WE DO NOT HAVE A RECORD OF AN EXISTING PERMITTED
 MECHANICAL SYSTEM. WE WILL HAVE TO REVIEW THIS AS A NEW
 SYSTEM. PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND PROVIDE A MECHANICAL DRAWING SHOWING
 THE DUCT WORK. PLEASE ALSO SHOW THE APPLIANCE ANCHORING
 DETAIL FOR THE CONDENSING UNIT. SHOW ON THE MECHANICAL
 DRAWING THE CONDENSATE PIPING AND THE TERMINATION
 LOCATION. FBC 107.2.1
  