| Plan Review Notes For Permit 21061609 |
| Permit Number |
21061609 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-19 13:43:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO CLEAR INDICATIONS ON ANY SUBMITTED PLAN | | | SHEET WHERE THE SITE WALL IS LOCATED, WHERE IT STARTS | | | AND STOPS. | | | | | | PLEASE PROVIDE SPECIFIC LOCATIONS. | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF ANY PROPOSED GATES OR | | | GATE LOCATIONS. | | | | | | PLEAE INDICATE IF ANY GATES ARE PROPOSED AND THEIR | | | LOCATIONS. | | | | | | ACTUAL GATES WILL NOT APPROVED UNDER THIS PERMIT. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|