| 2021-09-28 10:08:30 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 4TH REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: UPON PEER RIVEW OF THE ELEVATION CERTIFICATE, A |
| | CODE REQUIREMENT WAS MISSED ON THE LAST BLDG REVIEW. |
| | SEE BELOW: |
| | |
| | 1.STATEMENT BY DESIGNER ON PLANS REQUIRED. |
| | FBC R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD |
| | ELEVATION. |
| | 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS SHALL |
| | BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH |
| | SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE |
| | ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE |
| | ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS |
| | ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS |
| | SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN |
| | PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL |
| | PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON |
| | EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND |
| | EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF |
| | ASCE 24. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |