| Notes |
| Date |
Text |
| 2021-08-26 12:33:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLEASE SHOW HOW YOU CAN GO FROM A 40A TO 50A ON BUSS | | | ATTACHMENT? PLEASE READ THE REQUIREMENTS OF 240.4(B) | | | YOUR CALCULATION CAME OUT TO EXACTLY 40A. | | | | | | SIGNED CONTRACT NOT INCLUDED. |
|