| 2021-07-20 16:41:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | VALUE IS LOW. SUBMIT A SIGNED CONTRACT SHOWING COST OF | | | SOLAR, BATTERY, AND INSTALLATION (5600) | | | | | | RISER SHOWS 9870W OF PANELS WITH A 7800W INVERTER? | | | | | | RISER SHOW LG BATTERY CUT SHEETS SHOW DELTA BATTERY. | | | | | | RISER SHOW A 50A BREAKER ON A 200A BUSS PLEASE SHOW | | | CALCULATION ON HOW THIS COMPLIES WITH 705.12 |
|