| 2021-07-06 07:58:50 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21061546 | | | 7/6/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A REVISED WATER RISER DRAWING (P6.1) SHOWING | | | THE ADDITIONAL WATER LINE AND BACKFLOW PREVENTER AT THE | | | RO GENERATOR, AND THE REMOVAL OF THE RO LINES AND | | | BACKFLOW PREVENTERS AT THE STEAM STERILIZERS- SECTION | | | 107.2.1 WOPB, AND SECTION 608.3 FBC P. PLEASE NOTE THE | | | REMAINING SUPPLY LINES TO THE STERILIZERS AND ALL OTHER | | | WATER LINES TO STERILIZER CENTER EQUIPMENT SHALL BE | | | PROTECTED AGSINST BACKFLOW- SECTIONS 608.3 AND 608.3.1 | | | FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|