2021-07-06 07:58:501ST REVIEW FBC-2020 PLUMBING
 PERMIT-21061546
 7/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A REVISED WATER RISER DRAWING (P6.1) SHOWING
 THE ADDITIONAL WATER LINE AND BACKFLOW PREVENTER AT THE
 RO GENERATOR, AND THE REMOVAL OF THE RO LINES AND
 BACKFLOW PREVENTERS AT THE STEAM STERILIZERS- SECTION
 107.2.1 WOPB, AND SECTION 608.3 FBC P. PLEASE NOTE THE
 REMAINING SUPPLY LINES TO THE STERILIZERS AND ALL OTHER
 WATER LINES TO STERILIZER CENTER EQUIPMENT SHALL BE
 PROTECTED AGSINST BACKFLOW- SECTIONS 608.3 AND 608.3.1
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  