| Plan Review Notes For Permit 21061495 |
| Permit Number |
21061495 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-05 16:50:47 | NEITHER THE ENERGY CALCULATIONS OR THE DRAWINGS SHOW | | | THE GARAGE DOOR FOR THIS GARAGE. IS THERE A GARAGE DOOR | | | IN THIS GARAGE? PLEASE PROVIDE THE ENERGY CALCULATIONS | | | SHOWING THE VEHICLE GARAGE DOOR SIZE AND R-VALUE IN THE | | | CALCULATIONS. PLEASE CLEAN UP THE MECHANICAL DRAWING | | | AND SHOW THE LOT LINE AND THE PLACEMEN OF THE | | | CONDENSING UNIT. PLEASE SHOW THE ANCHORAGE DETAILS OF | | | THE CONDENSING UNIT. THE DESIGNER OF THE MECHANICAL | | | DRAWING MUST INCLUDE THEIR PRINTED NAME AND THEIR | | | SIGNATURE ON THE DRAWING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|