| Plan Review Notes For Permit 21061362 |
| Permit Number |
21061362 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-08 18:03:13 | 07/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | A SLAB REPAIR DETAIL WILL BE REQUIRED. SHOW THE WIDTH | | | OF THE | | | REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE O BE | | | REPLACED, | | | AND THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH | | | OF THE | | | DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING | | | SLAB, | | | AND THE SPACING OF THE DOWELS IN THE CENTER. THE REPAIR | | | SHALL | | | ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND THE | | | REQUIRED | | | VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE | | | CERTIFICATE | | | SHALL BE ONSITE FOR A FINAL INSPECTION. |
|