| 2021-07-23 15:51:26 | 4TH REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1)THE NEW SELECTED W-93 SYSTEM IS FOR NON-INSULATED |
| | ROOFS WITH MECHANICALLY ATTACHED BASE SHEET. THE |
| | PREVIOUS W-4 SYSTEM WAS FOR A MIN 1.5 INCH BASE |
| | INSULATION SYSTEM. PLEASE CLARIFY IF THE ROOF IS |
| | INSULATED OR NON-INSULATED. PLEASE NOTE THAT YOU HAVE |
| | PREVIOUSLY SUBMITTED FL. PRODUCT APPROVAL 491-R8 FOR |
| | CERTAINTEED INSULATION BOARD. I HAVE LOOKED THROUGH THE |
| | FL. PRODUCT APPROVAL 2533-R25 AND THERE ARE INSULATED |
| | SYSTEMS THAT EXCEED THE REQUIRED PRESSURE FOR CAT. C- |
| | ZONE 3. THE PREVIOUS REVIEW COMMENTS ARE LISTED BELOW. |
| | PLEASE COMPLY. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL2533-R25 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| | INCLUDE LIMITATIONS PAGE(S). |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-4 DO NOT MEET |
| | THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE |
| | REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT |
| | MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND |
| | SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | |
| | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | CHRISTOPHER L. COLE |
| | BUILDING PLANS EXAMINER |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH, FL. 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |