| 2021-08-20 10:36:18 | 1) THE FLOORS AND WALL BASES OF THE TOILET ROOMS SHALL |
| | COMPLY WITH FBC-BUILDING SEC. 1210.2.1.SHOW THE WALL |
| | FINISH ON THE PLANS. EPOXY PAINT ON DRYWALL DOES NOT |
| | COMPLY WITH THE CODE.2ND REQUEST. |
| | 2) SHOW THE RESTROOM AND MOP SINK WALL FINISH ON THE |
| | PLANS. THE WALL FINISH SHALL COMPLY WITH FBC-PLUMBING |
| | SEC.1210.2.2. EPOXY PAINT ON DRYWALL DOES NOT COMPLY |
| | WITH THE CODE. 2ND REQUEST. |
| | 3) THE MIRROR IN THE TOILET ROOM SHALL BE MEASURED A |
| | MAXIMUMOF 40 INCHES FROM THE FINISH FLOOR TO THE BOTTOM |
| | OF THE REFLECTIVE SURFACE PER FBC-ACCESS. SEC.603.3. |
| | 2ND REQUEST. |
| | 4) SHT. A2.0 - DETAIL #8 - RECESSED SOAP DISPENSER - |
| | THE OPERABLE PARTS SHALL BE WITHIN THE REACH RANGES PER |
| | SEC. 308 OF FBC-ACCESS. SHOW THE HEIGHT ON THE DETAIL. |
| | 2ND REQUEST. |
| | 5) SHT. A2.0 - DETAIL #6 - THE OPERABLE PARTS OF THE |
| | HCPT SHALL BE WITHIN THE REACH RANGES PER SEC. 308 OF |
| | FBC-ACCESS. SHOW THE HEIGHT ON THE DETAIL. 2ND REQUEST. |
| | 6) SHT. A2.0 - DETAIL #2 - THE TOILET PAPER DISPENSER |
| | SHALL COMPLY WITH FBC-ACCESS. SEC. 309.4 AND SHALL BE 7 |
| | INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER ( NOT TO THE CENTER OF THE FIRST DISPENSER. |
| | 2ND REQUEST. |
| | 7) SHT. A2.0 - DETAIL #1 & DETAIL #2 - THE GRAB BAR |
| | BEHIND THE WATER CLOSET IS SHOWN AS BEING MEASURED TO |
| | THE CENTERLINE OF THE GRAB BAR FROM THE FINISH FLOOR |
| | AND ALSO TO THE TOP OF THE BAR. THE GRAB BAR SHALL BE |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER |
| | FBC-ACCESS SEC. 609.4. 2ND REQUEST. |
| | 8) SHT. A2.0 - DETAIL #1 - THE GRAB BAR BEHIND THE |
| | WATER CLOSET SHALL BE LOCATED PER FBC-ACCESS. SEC. |
| | 604.5.2 & FIGURE 604.5.2.SHOW THE DIMENSIONS ON THE |
| | DETAIL. 2ND REQUEST. |
| | 9) SUBMIT A SANITARY AND WATER RISER FOR REVIEW FOR THE |
| | NEW PLUMBING WORK TO BE INSTALLED. WPB AMEND. TO FBC |
| | SEC. 1107.3.5.1.3. |
| | 10) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE |
| | WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| | EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING |
| | MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS |
| | ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE |
| | TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER |
| | OVER WELL COMPACTED SOIL. A COPY OF THE TERMITE |
| | CERTIFICATE SHALL BE ONSITE FOR FINAL INSPECTION. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |