| 2021-08-11 08:13:57 | REVISION - BUILDOUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE SHOW RESTROOM FLOOR AND BASE BOARD TO COMPLY |
| | WITH FBC 1210.2.1FLOORS AND WALL BASES. |
| | IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| | SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| | FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| | WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE FOR THE BASE BOARD) |
| | 2) PLEASE SHOW RESTROOM AND MOP SINK AREA WALL FINISH |
| | TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE). |
| | 3) (NO CHANGES) PLEASE SHOW ACCESSIBLE RESTROOM MIRRORS |
| | MAXIMUM HEIGHT FROM THE FINISHED FLOOR TO THE BOTTOM OF |
| | THE "REFLECTIVE SURFACE" FBC (A) 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 4) NEW DRAWINGS NEED TO BE IN THE "DRAWINGS" FOLDER IN |
| | PROJECTDOX. DRAWINGS IN THE "SIGNATURE" FOLDER IN |
| | PROJECTDOX CANNOT BE MARKED APPROVED. IF NEEDED ADD TO |
| | BOTH "SIGNATURES" AND "DRAWINGS" FOLDER. |
| | |