2021-07-01 09:50:1507/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE AT THE FIELD, AND IF NOT TO CODE, IT MAY
 NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE OWNER'S
 EXPENSE.
  
 2. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. PLEASE CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS
 OF PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1. THE 14 FT PROVIDED IS NOT CORRECT.
 SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2020 FBC FG RES. TABLE G2413.4
 (12) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 5. PLEASE PROVIDE SIZE OF PIPE FROM METER TO DRYER AREA
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413. ( THE GAS DRYER HAS NO BTU?S AND THE TOTAL IS
 NOT CLEAR)
  
 8. THIS HOME HAS AN EXISTING GAS METER AND EQUIPMENT.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 TO THE SYSTEM'S TOTAL BTU LOAD TO ENSURE THE EXISTING
 SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION PER THE 2020 FBC
 RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
  
 9. PLEASE LABEL REGULATOR PER THE 2020 FBC RES. SEC
 G2421.2.
  
 10. PLEASE SHOW AND LABEL DRIP LEG AND SHUTOFF VALVES
 ON GAS ISOMETRIC PER THE 2020 FBC RES. SEC. G2419.2.
  
 11. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  