| 2021-06-24 11:27:37 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21061264 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR CHANGING |
| | THE GARAGE INTO A CONDITIONED SPACE. FBC EC 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THE NEWLY CONDITIONED SPACE OF THE |
| | GARAGE. FBC EC R403.7, FBC RES M1401.3 |
| | |
| | 3) IS THE NEW HVAC A LIKE FOR LIKE CHANGE OUT? IF IT IS |
| | PLEASE PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM. IF |
| | THIS IS NOT A LIKE FOR LIKE CHANGE OUT PLEASE PROVIDE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1 |
| | |
| | 4) PLEASE SHOW THE ANCHORAGE METHOD USED FOR THE NEW |
| | OUTDOOR CONDENSING UNITS. FBC RES M1307.2 |
| | |
| | 5) SHEET A1.0 NOTE 18 IS CALLING FOR A NEW HVAC SYSTEM |
| | UPSTAIRS. PLEASE PROVIDE A MECHANICAL DRAWING FOR THIS |
| | NEW WORK. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |