| Plan Review Notes For Permit 21061234 |
| Permit Number |
21061234 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-29 14:31:43 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY THIS AS AN R-3 OCCUPANCY. THIS | | | BUILDING CONTAINS MORE THAN TWO DWELLING UNITS (CONDO) | | | AND IS CLASSIFIED AS AN R-2 OCCUPANCY. FBC CHAPTER 3 | | | | | | 2) THE WINDLOAD DATA INCORRECTLY SPECIFIES ASCE10-05. | | | THE 2020 FBC REFERENCES ASCE7-16 FOR WIND DESIGN. FBC | | | CHAPTER 35 | | | | | | 3) THE EXPOSURE CATEGORY IS SPECIFIED AS B. THE | | | EXPOSURE CATEGORY FOR THIS BUILDING SHOULD BE C. FBC | | | 1609 | | | | | | 4) SUBMIT THE SPECIFICATIONS WITH ALLOWABLE SPANS ALONG | | | WITH THE INSTALLATION INSTRUCTIONS FOR THE COMPOSITE | | | DECKING. FBC 1605 AND FBC AMEND. 107.1.2 | | | | | | 5) THE UNIFORM LIVE LOADS FOR THE STAIRS IS 100 PSF PER | | | FBC TABLE 1607.1. PLEASE SPECIFY THIS ON THE PLANS. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | |
|