| Plan Review Notes For Permit 21061218 |
| Permit Number |
21061218 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-08-30 07:51:40 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21061218 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-3: A/C UNIT SCHEDULE INDICATES RTU-1A, | | | RTU-1B, RTU-2A, RTU-2B. SHEET M-1 DOES NOT SHOW THESE | | | UNITS. WHERE ARE THESE UNITS LOCATED? | | | | | | 2) SHEET M-3: WHY ARE RTU-3 AND RTU-4 COUNTED IN THE | | | AIR BALANCE SCHEDULE AS THEY ARE NOT IN THE A-2 TENANT | | | SPACE? | | | | | | 3) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING | | | THE HOODS WILL REQUIRE A SEPARATE PERMIT APPLICATION, | | | DRAWINGS AND REVIEW. THE HOOD WILL NOT BE REVIEWED | | | UNDER THIS PERMIT. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|