| 2021-07-13 16:29:40 | 07/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-1; |
| | |
| | A. IN RESTROOM 109, THE LAV INS ENCROACHING IN THE |
| | CLEAR FLOOR SPACE FOR THE CLEAR FLOOR SPACE SHALL BE |
| | 60" INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| | SIDEWALL, AND 56? INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | B. PLEASE DETAIL OR SHOW ACCESSIBLE DIMENSIONS FOR |
| | FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | |
| | 2. ON SHEET A-3; |
| | A. THE PLANS ARE CUT OFF ON THE TOP PART. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. PLEASE SHOW THE TURNING SPACE DIAMETER- SPACE THAT |
| | SHALL BE A SPACE OF 60 INCHES DIAMETER MINIMUM PER THE |
| | 2020 FBC ACC SEC. 304.3. |
| | |
| | C. THE MIRROR'S REFLECTIVE PART NEEDS TO BE 40 INCHES |
| | TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3. |
| | |
| | D. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS. |
| | |
| | E. PLEASE PROVIDE DETAIL ON HOW GRAB BARS REINFORCE IN |
| | WALLS. WOULD YOU PLEASE SHOW THE MINIMUM AND MAXIMUM |
| | DISTANCE FROM THE FLOOR PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON SHEET P-1; |
| | STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL |
| | SYSTEMS. A. THE HAND SINKS ARE NOT ALLOWED TO GO INTO |
| | THE GREASE INTERCEPTOR. PLEASE REFER TO 64E-6, FLORIDA |
| | ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE |
| | SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP |
| | SINK SHALL GO INTO THE GREASE INTERCEPTOR. |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON REMARKS? |
| | |
| | 4. ON SHEET P-2; |
| | STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL |
| | SYSTEMS. A. PLEASE SHOW THE MOP SINK GOING INTO THE |
| | GREASE INTERCEPTOR, REFER TO 64E-6, FLORIDA |
| | ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE |
| | SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP |
| | SINK SHALL GO INTO THE GREASE INTERCEPTOR. |
| | |
| | B. HAND SINK IN THE KITCHEN AREA ARE SHOWN GOING INTO |
| | GREASE INTERCEPTORS WHICH ARE NOT ALLOWED; REFER TO |
| | 64E-6, FLORIDA ADMINISTRATIVE CODE FOR PROPER |
| | DISPLACEMENT TO THE SANITARY OR GREASE INTERCEPTOR PER |
| | THE 64E-6. STANDARDS FOR ONSITE SEWAGE TREATMENT AND |
| | DISPOSAL SYSTEMS. |
| | |
| | 5. ON SHEET P-3; |
| | |
| | A. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| | REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1. |
| | |
| | B. PLEASE PROVIDE A SHUTOFF VALVE ON BOTH SIDES OF THE |
| | RECIRCULATING PUMP PER THE 2020 FBC SEC. P 606.2 #3. |
| | ALSO, SHOW ON HEATER DETAIL P-700 #11. |
| | |
| | C. PLEASE PROVIDE A HAMMER ARRESTOR ON THE WARE-WASHER |
| | AND ANY OTHER QUICK CLOSING VALVE PER THE 2020 FBC SEC. |
| | 604.9. |
| | |
| | D. WATER TO EACH STRUCTURE SHALL HAVE A SUPPLY PIPE AT |
| | THE ENTRANCE INTO THE SHUT-OFF VALVE PER THE 2020 FBC |
| | 606.1 #2 LOCATION OF FULL-OPEN VALVES. |
| | |
| | 6. ON SHEET P-4, UNDER PLUMBING FIXTURE SCHEDULE FOR |
| | INLINE BACKFLOW PREVENTER, 1022 ARE FOR SODA MACHINES |
| | AND WITH A CARBONATION WATER OVERFLOW AND REQUIRE A |
| | DRAIN PER THE 2020 FBC SEC. 608.17.1.1., THE 1024 |
| | INLINE BACKFLOW PREVENTER ARE FOR ICEMAKER AND COFFEE |
| | MAKER PER THE 2020 FBC SEC. 608.17.1.2. WOULD YOU |
| | PLEASE CORRECT WHICH WILL BE USED? |
| | |
| | 7. ON SHEET P-5; PLEASE PROVIDE DETAIL FOR THE |
| | MULTIPLE-COMPARTMENT SINK SHOWING THE DISCHARGE |
| | INDEPENDENTLY TO A WASTE RECEPTOR PER THE 2020 FBC P |
| | 802.1.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |