Plan Review Notes
Plan Review Notes For Permit 21061201
Permit Number 21061201
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-14 09:54:28BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/RPX306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: SHUTTER SCHEDULE
  
 1. FASTENERS MUST BE SPECIFIC FROM FASTENER SCHEDULE.
 SEE NOTE #1 ON SHUTTER SCHEDULE.
 AVAILABLE FASTENERS ARE: 1/4" ITW TAPCONS OR DEWALT
 ULTRACON WITH 1 3/4" EMBEDDMENT.
  
 CORRECT SHUTTER SCHEDULE AND RE-SUBMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.