| 2021-06-29 16:01:34 | 06/29/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 2. PLEASE CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 4. THIS HOME HAS AN EXISTING GAS METER AND EQUIPMENT. |
| | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| | TO THE SYSTEM'S TOTAL BTU LOAD TO ENSURE THE EXISTING |
| | SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 5. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR THE GENERATOR TO VERIFY |
| | COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 7. PLEASE SHOW DRIP LEG AND SHUTOFF VALVES ON GAS |
| | ISOMETRIC PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |