| Plan Review Notes For Permit 21061179 |
| Permit Number |
21061179 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-09 10:37:53 | PLAN REVIEW BUILDING GENERATOR | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: PROVISO ON PLAN PAGE P-1. TOP OF STRUCTURAL GEN | | | PAD SHALL BE AT OR ABOVE FINISHED FLOOR ELEVATION. | | | | | | 1. THE GEN PAD DETAIL AND DESIGN WIND LOADS ARE BASED | | | ON THE 2010 FBC AND ASCE 7-10. PROVIDE STRUCTURAL | | | DETAIL AND WIND LOADS BASED ON THE 2020 FBC AND ASCE | | | 7-16. | | | | | | 2. GENERATOR LOCATION | | | R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|