Plan Review Notes
Plan Review Notes For Permit 21061179
Permit Number 21061179
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-09 10:37:53PLAN REVIEW BUILDING GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PROVISO ON PLAN PAGE P-1. TOP OF STRUCTURAL GEN
 PAD SHALL BE AT OR ABOVE FINISHED FLOOR ELEVATION.
  
 1. THE GEN PAD DETAIL AND DESIGN WIND LOADS ARE BASED
 ON THE 2010 FBC AND ASCE 7-10. PROVIDE STRUCTURAL
 DETAIL AND WIND LOADS BASED ON THE 2020 FBC AND ASCE
 7-16.
  
 2. GENERATOR LOCATION
 R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  