| Plan Review Notes For Permit 21061171 |
| Permit Number |
21061171 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-06-24 16:02:12 | 4TH REVIEW FBC-2020 PLUMBING | | | PERMIT- 21061171 | | | 6/24/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED MANUFACTURER'S SPECIFICRTIONS FOR THE | | | ARCHIE AR031 SHOWER VALVE DO NOT INDICATE COMPLIANCE | | | WITH SEC. 412.3 FBC P- INDIVIDUAL SHOWER AND TUB-SHOWER | | | COMBINATION VALVES SHALL BE BALANCED-PRESSURE, | | | THERMOSTATIC OR COMBINATION | | | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO | | | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA | | | B125.16 OR ASME A112.18.1/CSA B125.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|